Earth the car?
I'm thinking of building in one of those Lidl battery chargers in the old
car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? -- *Always borrow money from pessimists - they don't expect it back * Dave Plowman London SW To e-mail, change noise into sound. |
#2
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Dave Plowman (News) wrote:
I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. |
#3
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Dave Osborne gurgled happily, sounding much like
they were saying: I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Motorbike Optimate-style. |
#4
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
On 16 Dec 2009 09:51:33 GMT, Adrian wrote:
Dave Osborne gurgled happily, sounding much like they were saying: I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Motorbike Optimate-style. That's what I have done. My Halfords 'maintenance' charger came with both croc clips and also a set of flying leads that could be permanently bolted to the battery terminals with an in-line shrouded connector that matches the one on the charger. So to do a trickle charge, I simply open the bonnet and quickly hook up the flying leads to the charger. A red/green led indicates when the battery is fully charged. David |
#5
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
On 16 Dec, 09:51, Adrian wrote:
Dave Osborne gurgled happily, sounding much like they were saying: I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Motorbike Optimate-style. The extra-low voltage option would be by far the safest solution. If you really do want to put a 230v mains supply into the car then use a 3 core flex with a trailing socket and a 3 pin mains rated connector at the car end. Earth the car via the earth pin of the connector. Also use a supply with 30mA RCD protection (which all sockets rated at less than 20A, intended to supply equipment for use out of doors should have for additional personal protection in the event of a fault) |
#6
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
On 16 Dec, 09:51, Adrian wrote:
Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Voltage drop in the cables screws with measuring float voltage. Where this is done commercially, it's a 4-lead setup back to the sense input. |
#7
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In article
, Andy Dingley wrote: On 16 Dec, 09:51, Adrian wrote: Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Voltage drop in the cables screws with measuring float voltage. Where this is done commercially, it's a 4-lead setup back to the sense input. Rather guessed something like that would apply. -- *Be nice to your kids. They'll choose your nursing home. Dave Plowman London SW To e-mail, change noise into sound. |
#8
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
On Wed, 16 Dec 2009 04:39:49 -0800 (PST), Andy Dingley wrote:
On 16 Dec, 09:51, Adrian wrote: Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Voltage drop in the cables screws with measuring float voltage. Where this is done commercially, it's a 4-lead setup back to the sense input. How about a nice hefty battery cable to a proper Anderson connector? You can keep only the low voltage on the car then and there'd be next to no voltage drop on the extra length of cable with the low current of a charger and the large CSA. You'd also have the added bonus that you could use the connector for a plug in set of jump leads. I keep meaning to get around to doing this on my kit-car. SteveW |
#9
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In article ,
Adrian wrote: Dave Osborne gurgled happily, sounding much like they were saying: I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. Or do it the other way round, and plug the low-voltage into the car, keeping the charger. Motorbike Optimate-style. I'd rather a neater way. The charger will fit nicely in a dead space alongside the spare wheel. -- *Very funny Scotty, now beam down my clothes. Dave Plowman London SW To e-mail, change noise into sound. |
#10
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Dave Osborne pretended :
No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. I do it the other way around... Lidl charger is in a bracket, up in the garage roof, with a 12v cable fitted with a ciggy plug dangling down to car. As I park, I pull the ciggy plug in and plug it in. The ciggy socket has to be the type which is on all the time, which depends upon the car. -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk |
#11
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
The ciggy socket has to be the type which is on all the time, which depends upon the car. I have wondered why that varies between manufacturers. Mine does, and it's very useful to leave a camera or phone tucked away and on charge sometimes. |
#13
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In message
, " writes The ciggy socket has to be the type which is on all the time, which depends upon the car. I have wondered why that varies between manufacturers. Worse than that, it varies between models from the same manufacturer. Bloody stupid idea. Mine does, and it's very useful to leave a camera or phone tucked away and on charge sometimes. -- Clint Sharp |
#14
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In article ,
Harry Bloomfield wrote: Dave Osborne pretended : No. If the battery charger is double insulated, then the only issue is preventing the chassis becoming live from a fault on the mains cable. Cover the mains lead in plastic conduit and ensure that it can't chafe or snag on anything. Make sure you plug in to an RCD-protected supply. I do it the other way around... Lidl charger is in a bracket, up in the garage roof, with a 12v cable fitted with a ciggy plug dangling down to car. As I park, I pull the ciggy plug in and plug it in. The ciggy socket has to be the type which is on all the time, which depends upon the car. That's fine if you have a garage... -- *Why 'that tie suits you' but 'those shoes suit you'?* Dave Plowman London SW To e-mail, change noise into sound. |
#15
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
"Dave Plowman (News)" wrote in message ... I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? -- *Always borrow money from pessimists - they don't expect it back * Dave Plowman London SW To e-mail, change noise into sound. How about "dodgem car" style. Park one wheel on a metal plate and some kind of ceiling contact. Ground the plate as well. I've got no idea how many ohms a tyre would present in circuit...but surely a small enough figure to trickle charge a battery? |
#16
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Vortex4 explained :
Park one wheel on a metal plate and some kind of ceiling contact. Ground the plate as well. I've got no idea how many ohms a tyre would present in circuit...but surely a small enough figure to trickle charge a battery? Several megs at least, so no. -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk |
#17
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
explained :
On Wed, 16 Dec 2009 11:06:50 -0000, "Vortex4" wrote: "Dave Plowman (News)" wrote in message ... I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. How about "dodgem car" style. Park one wheel on a metal plate and some kind of ceiling contact. Ground the plate as well. I've got no idea how many ohms a tyre would present in circuit...but surely a small enough figure to trickle charge a battery? Many many years ago when I had a vehicle with an unreliable battery I did something like that. Two radio aerials on the car roof one connected to + other to the body work. Hanging in the garage a couple of wire coat hangers stuck in a wooden beam and connected to the charger. aerials touched hangers and connection made without faffing around with plugs. G.harman To do that the more modern way, you would have the mains connected primary winding of a transformer hanging from the ceiling at a suitable height and the secondary winding on the car roof. -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk |
#18
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Harry Bloomfield
wibbled on Saturday 19 December 2009 10:24 To do that the more modern way, you would have the mains connected primary winding of a transformer hanging from the ceiling at a suitable height and the secondary winding on the car roof. Then park it round the side of the MI5 building, retreat behind a tree with a videocam and post on youtube. -- Tim Watts This space intentionally left blank... |
#19
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
This is actually something that was covered in the most recent edition
(17th) of the wiring regulations, in relation to power hook-ups in caravans and motorhomes. Basically the regs say that caravans and motorhomes must have metallic bodies/chassis earth bonded, along with RCD protection on the hook-up. Presumably the reasoning behind bonding is that should there be a fault that caused the body to become live, it could present the most dangerous scenario of someone barefoot outside the vehicle touching live bodywork. That's all well and good in places like UK campsites with properly tested hook-ups that have both a good earth and RCD protection. It's not so good on places where there's a dodgy earth, or the possibility of live/earth being transposed. So - practically - do what you feel is safest in the locations you will use your charger hook-up. Not bonding and carefully protecting the cable sounds reasonable, if you're the only user and use it in locations you trust. An approach popular with many van users is to use a "tent power hook- up". This is basically a mains plug on one end (often a commando) and a mini-consumer unit on the other. e.g. http://www.camping-caravan-outdoors....f.asp?item=876 With some vehicles (well VW T4 vans for definite) you can pop a reflector out of the rear bumper and feed the plug and lead from the consumer unit outside the vehicle, or even mount a connector there. On untrusted locations, one of those mains test plugs to check polarity of the wiring and the presence of some sort of earth, is a cheap and quick way of getting an indication that all may not be well. |
#20
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In article
, wrote: This is actually something that was covered in the most recent edition (17th) of the wiring regulations, in relation to power hook-ups in caravans and motorhomes. Basically the regs say that caravans and motorhomes must have metallic bodies/chassis earth bonded, along with RCD protection on the hook-up. Thanks - that's what I'll do. Although I wasn't intending having any mains outlets in the car. ;-) -- *If you can read this, thank a teecher Dave Plowman London SW To e-mail, change noise into sound. |
#21
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
On Wed, 16 Dec 2009 09:24:16 +0000, Dave Plowman (News) wrote:
I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? FWIW, engine block heaters and battery conditioners are *very* common in these parts - I'm not aware of any of them typically being grounded, but then they always seem to have a little bit of trailing flex and socket, rather than a socket mounted rigidly to the vehicle's body. (I'm not sure how well a cheap battery charger will stand up to permanent connection and repeated starts with it connected? I expect - but don't know for sure - that a proper conditioner is designed to be a bit more robust in that regard) cheers Jules |
#22
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In article . com,
Jules wrote: (I'm not sure how well a cheap battery charger will stand up to permanent connection and repeated starts with it connected? I expect - but don't know for sure - that a proper conditioner is designed to be a bit more robust in that regard) The Lidl charger is only cheap in price. It's an extremely sophisticated design. Those 'proper' conditioners are often a con price wise - for what amounts to little more than low power DC supply with a few added components. -- *I have my own little world - but it's OK...they know me here* Dave Plowman London SW To e-mail, change noise into sound. |
#23
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
on 16/12/2009, Dave Plowman (News) supposed :
The Lidl charger is only cheap in price. It's an extremely sophisticated design. Those 'proper' conditioners are often a con price wise - for what amounts to little more than low power DC supply with a few added components. Agreed, I have three or four of them. One permanently set up to maintain the car in the garage, one on the tractor, one in the caravan, and a spare around somewhere - with an Optimate keeping the bikes battery ready to go. -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk |
#24
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Jules submitted this idea :
(I'm not sure how well a cheap battery charger will stand up to permanent connection and repeated starts with it connected? I expect - but don't know for sure - that a proper conditioner is designed to be a bit more robust in that regard) They (Lidl unit) will be fine. I have one in use like that for a few years. My car can at times sit in the garage unused for weeks, so it is often left with a Lidl unit connected. I have also had it charge flat batteries up and it gets no more than luke warm. The only down side, is if the mains goes off briefly - you need to press a button to restart the charge. -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk |
#25
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Dave Plowman (News) wrote:
I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? I would say yes. Treat the whole car as an appliance - it has a metal case and can't be certified as double insulated, so the case must be earthed. Things get more complex for a boat, where galvanic corrosion in salt water needs to be considered, but for a car I'd certainly connect the body to the earth in the connector. Pete |
#26
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
After serious thinking Pete Verdon wrote :
I would say yes. Treat the whole car as an appliance - it has a metal case and can't be certified as double insulated, so the case must be earthed. Things get more complex for a boat, where galvanic corrosion in salt water needs to be considered, but for a car I'd certainly connect the body to the earth in the connector. No one has suggested an earth rod ) -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk |
#27
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
"Harry Bloomfield" wrote in message . uk... After serious thinking Pete Verdon wrote : I would say yes. Treat the whole car as an appliance - it has a metal case and can't be certified as double insulated, so the case must be earthed. Things get more complex for a boat, where galvanic corrosion in salt water needs to be considered, but for a car I'd certainly connect the body to the earth in the connector. No one has suggested an earth rod ) -- Regards, Harry (M1BYT) (L) http://www.ukradioamateur.co.uk That is because it is not an Audi TT. Adam |
#28
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Pete Verdon d
wibbled on Wednesday 16 December 2009 20:05 Dave Plowman (News) wrote: I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? I would say yes. Treat the whole car as an appliance - it has a metal case and can't be certified as double insulated, so the case must be earthed. Things get more complex for a boat, where galvanic corrosion in salt water needs to be considered, but for a car I'd certainly connect the body to the earth in the connector. Pete I would agree with that. Earthing the car will be a better bet IMHO than trying to insure that there is no way that a mains cable entering the car cannot become damaged on a sharp with of metal and become live. Another way would be to take the double insulated approach, but to use SY flex to take the mains in and earth the braid. That flex doesn't meet the mechanical protection criteria of the IEE regs in way that armoured does, but looking at it objectively, if the outer sheath does become cut, it will provide some mechanical and electrical protection. But the obvious belt and braces approach, as others have mentioned is to talk SELV into car. Might be worth having a look at some engine preheaters - those are mains - see what they do regarding earthing. -- Tim Watts This space intentionally left blank... |
#29
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Tim W wrote:
Earthing the car will be a better bet IMHO than trying to insure that there is no way that a mains cable entering the car cannot become damaged on a sharp with of metal and become live. Another way would be to take the double insulated approach, but to use SY flex to take the mains in and earth the braid. As long as you're not planning to take the SY flex into the battery charger, which would defeat the double-insulated properties of the charger and be more dangerous! That flex doesn't meet the mechanical protection criteria of the IEE regs in way that armoured does, but looking at it objectively, if the outer sheath does become cut, it will provide some mechanical and electrical protection. But the obvious belt and braces approach, as others have mentioned is to talk SELV into car. Might be worth having a look at some engine preheaters - those are mains - see what they do regarding earthing. It's worth pointing out that the reason Caravans and motor homes are required to be earthed is because human beings occupy them naked and wet when the mains electricity is connected. In Dave's case, he's going to be fully dressed and he's going to disconnect the mains before he gets into the car, so the risk of electric shock is minimal. However, there's no obvious downside to fitting a 3-pin inlet to the car and earthing to the chassis/body. He should not under any circumstances, however, consider modifying the charger from Class II to Class I (i.e double insulated to earthed). Cheers, DaveyOz |
#30
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Dave Osborne
wibbled on Thursday 17 December 2009 17:43 Tim W wrote: Earthing the car will be a better bet IMHO than trying to insure that there is no way that a mains cable entering the car cannot become damaged on a sharp with of metal and become live. Another way would be to take the double insulated approach, but to use SY flex to take the mains in and earth the braid. As long as you're not planning to take the SY flex into the battery charger, which would defeat the double-insulated properties of the charger and be more dangerous! No, I was thinking of the SY flex being the flying lead used to plug the charger into the house supply - that being the bit that is vulnerable to chafing. The charger and its immediate wiring can be secured and protected. I'm not sure I entirely agree that feeding an earth shielded flex into a Class II appliance makes it dangerous though. What failure scenarios could that cause that would result in a dangerous condition? -- Tim Watts This space intentionally left blank... |
#31
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
Tim W wrote:
Dave Osborne wibbled on Thursday 17 December 2009 17:43 Tim W wrote: Earthing the car will be a better bet IMHO than trying to insure that there is no way that a mains cable entering the car cannot become damaged on a sharp with of metal and become live. Another way would be to take the double insulated approach, but to use SY flex to take the mains in and earth the braid. As long as you're not planning to take the SY flex into the battery charger, which would defeat the double-insulated properties of the charger and be more dangerous! No, I was thinking of the SY flex being the flying lead used to plug the charger into the house supply - that being the bit that is vulnerable to chafing. The charger and its immediate wiring can be secured and protected. I'm not sure I entirely agree that feeding an earth shielded flex into a Class II appliance makes it dangerous though. What failure scenarios could that cause that would result in a dangerous condition? Class II appliances are designed such that if a live wire goes astray inside the unit, there is no external metalwork which can become live. (this is not, I stress, saying that there would be no external metalwork at all). In the event of a fault the unit will simply stop working or pop a fuse (thermal or over-current), rather than become hazardous to touch. This allows the manufacturer of the product to make the internal chassis live, to have various different bits of internal metalwork at different potentials, etc. This, in turn, facilitates value engineering the design for minimal production costs. It also allows the product designer to create a product with mixed metal and plastic components (e.g. a hand-held electric drill) without needing to ensure that there is contiguous earth bonding within the unit. By introducing an earth wire (or indeed armour/screening) into the interior of the unit, you would then effectively make it a Class I appliance. You would then have to make an electrical safety reassessment of the product design. Depending on the nature of the product this could be straightforward or it could be virtually impossible to achieve without extensive design reworking. |
#32
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In message , "Dave Plowman (News)"
writes I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? I can go for several months without driving my car, but I do have a good battery in it (and a solar plug in the cigarette lighter charger). I just don't have problems -- geoff |
#33
Posted to uk.d-i-y
|
|||
|
|||
Earth the car?
In article ,
geoff wrote: I'm thinking of building in one of those Lidl battery chargers in the old car. So it can be left on float when not in use. The mains lead on those is only two core and the case plastic. I was considering a Buccaneer weather proof mains connector mounted in the body below the rear bumper. Should the car body be connected to mains earth? I can go for several months without driving my car, but I do have a good battery in it (and a solar plug in the cigarette lighter charger). I just don't have problems I've got a fairly high quiescent draw on it - lots of extra junk fitted. ;-) -- *Reality? Is that where the pizza delivery guy comes from? Dave Plowman London SW To e-mail, change noise into sound. |