Is there a safe, possibly double insulated, means to derive a 12V DC power
supply when the motor control cabinet only has three phases or must I bring
an earth and neutral into the cabinet and connect a 240V wall wart to it?
This is to provide power to a gsm telemetry module.

If it is doable where might I buy one?

AJH
  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,158
Default 12V power supply derived from 3ph


"andrew" wrote in message
...
Is there a safe, possibly double insulated, means to derive a 12V DC

power
supply when the motor control cabinet only has three phases or must

I bring
an earth and neutral into the cabinet and connect a 240V wall wart

to it?
This is to provide power to a gsm telemetry module.

If it is doable where might I buy one?

AJH


415v to 240v transformer feeding your wall wart - three phase has 415v
phase to phase and 240 (ish) phase to neutral so you take any two
phases as the 415v input to your transformer. Such transformers widely
used to power lights and such like on industrial machine with no
neutral feed. RS components stock them.

AWEM

  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 477
Default 12V power supply derived from 3ph

Andrew Mawson wrote:

415v to 240v transformer feeding your wall wart - three phase has 415v
phase to phase and 240 (ish) phase to neutral so you take any two
phases as the 415v input to your transformer. Such transformers widely
used to power lights and such like on industrial machine with no
neutral feed. RS components stock them.


Thanks Andrew, that prompted me to have a look and JMS transformers made me
one with a 415V primary and 240V secondary ( for a heating time switch)
plus a 18V secondary with rectifier and smoothing capacitor (to supply the
gps device) Wired it all in today and it seems to work, as things are a bit
cramped I will check how warm everything gets in the morning.

AJH
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,158
Default 12V power supply derived from 3ph


"andrew" wrote in message
...
Andrew Mawson wrote:

415v to 240v transformer feeding your wall wart - three phase has

415v
phase to phase and 240 (ish) phase to neutral so you take any two
phases as the 415v input to your transformer. Such transformers

widely
used to power lights and such like on industrial machine with no
neutral feed. RS components stock them.


Thanks Andrew, that prompted me to have a look and JMS transformers

made me
one with a 415V primary and 240V secondary ( for a heating time

switch)
plus a 18V secondary with rectifier and smoothing capacitor (to

supply the
gps device) Wired it all in today and it seems to work, as things

are a bit
cramped I will check how warm everything gets in the morning.

AJH


Glad to help, nice to hear of a good result.

AWEM

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
HP/Agilent E3632A programmable power supply has power up failure (solution) JW Electronics Repair 0 September 20th 07 11:54 AM
power supply heating problem [6/6] "MEDIUM POWER 2uS tb.jpg" (1/1) No Name Electronic Schematics 0 April 15th 07 10:14 PM
power supply heating problem [2/6] "HIGH POWER 2uS tb.jpg" (1/1) No Name Electronic Schematics 0 April 15th 07 10:13 PM
ATX power supply to bench supply conversion Kingcosmos Electronics Repair 5 April 4th 07 04:24 PM
X-Box power surge - blew out switching power supply [email protected] Electronics Repair 0 December 25th 04 02:33 PM


All times are GMT +1. The time now is 02:15 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"