Can anyone point me to a source of meter tails bigger than 35mm? I'm
having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) but no one seems to stock it. Any pointers gratefully received. AWEM |
#2
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
In article ,
Andrew Mawson wrote: Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) but no one seems to stock it. Any pointers gratefully received. TLC will supply it in cut lengths - but to order as branches don't stock it. -- *Organized Crime Is Alive And Well; It's Called Auto Insurance. Dave Plowman London SW To e-mail, change noise into sound. |
#3
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Andrew Mawson wrote:
Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) Table 4D1A, 70 deg. PVC singles, Ref. method F (free air or perforated tray), 3-phase, cables touching in trefoil formation: - 35 mm^2 - 137 amps - 50 mm^2 - 167 amps - 70 mm^2 - 216 amps. but no one seems to stock it. Any pointers gratefully received. Try the more industrial orientated wholesalers like Newey & Eyre or CSE (http://cse-distributors.co.uk/cable/index.htm). -- Andy |
#4
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]() "Andy Wade" wrote in message ... Andrew Mawson wrote: Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) Table 4D1A, 70 deg. PVC singles, Ref. method F (free air or perforated tray), 3-phase, cables touching in trefoil formation: - 35 mm^2 - 137 amps - 50 mm^2 - 167 amps - 70 mm^2 - 216 amps. but no one seems to stock it. Any pointers gratefully received. Try the more industrial orientated wholesalers like Newey & Eyre or CSE (http://cse-distributors.co.uk/cable/index.htm). -- Andy Andy thanks for that. Is there a derating factor as its in 100mm square pvc trunking or does that count as free air? AWEM |
#5
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Andrew Mawson wrote:
Andy thanks for that. Is there a derating factor as its in 100mm square pvc trunking or does that count as free air? You'll be needing 70 mm^2 then... Table 4D1A, ref. method B (enclosed in conduit or trunking on a non-thermally-insulating wall), 3 or 4 cables 3-ph AC: - 35 mm^2 - 110 amps - 50 mm^2 - 134 amps - 70 mm^2 - 171 amps - 95 mm^2 - 207 amps -- Andy |
#6
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On 19 Dec, 09:11, "Andrew Mawson"
wrote: Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) but no one seems to stock it. Any pointers gratefully received. AWEM City Electrical Factors. |
#7
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]() wrote in message ... On 19 Dec, 09:11, "Andrew Mawson" wrote: Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) but no one seems to stock it. Any pointers gratefully received. AWEM City Electrical Factors. Thanks Mark, TLC have got them for me - should arrive Mon/Tuesday - ended up having to use 70mm AWEM |
#8
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Andrew Mawson wrote:
wrote in message ... On 19 Dec, 09:11, "Andrew Mawson" wrote: Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) but no one seems to stock it. Any pointers gratefully received. AWEM City Electrical Factors. Thanks Mark, TLC have got them for me - should arrive Mon/Tuesday - ended up having to use 70mm Good luck bending the buggers ;-) -- Cheers, John. /================================================== ===============\ | Internode Ltd - http://www.internode.co.uk | |-----------------------------------------------------------------| | John Rumm - john(at)internode(dot)co(dot)uk | \================================================= ================/ |
#9
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On Sun, 21 Dec 2008 03:03:19 +0000, John Rumm wrote:
Andrew Mawson wrote: wrote in message ... On 19 Dec, 09:11, "Andrew Mawson" wrote: Can anyone point me to a source of meter tails bigger than 35mm? I'm having a three phase 160amp per phase supply to a workshop, need probably 50mm tails (anyone able to confirm??) but no one seems to stock it. Any pointers gratefully received. AWEM City Electrical Factors. Thanks Mark, TLC have got them for me - should arrive Mon/Tuesday - ended up having to use 70mm Good luck bending the buggers ;-) Linesmen used to use extra large ring spanners[1] to get sets into the Henlite[2] cables for connection onto pole transformers. [1] 3/4 x 7/8 whit from memory [2] Trade name, insulated and sheathed Ali cable, largest size used to be 120mm˛ I think. -- The Wanderer Better to keep one's mouth shut and be thought a fool Than to open it and remove all doubt (Mark Twain) |
#10
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
In article ,
"The. Wanderer" writes: Linesmen used to use extra large ring spanners[1] to get sets into the Henlite[2] cables for connection onto pole transformers. [1] 3/4 x 7/8 whit from memory [2] Trade name, insulated and sheathed Ali cable, largest size used to be 120mm˛ I think. I've got a piece of 150mm˛ here (11kV)... It's only 14" long so you can't get much leverage, but might as well be rock solid (overall dia = 31mm). -- Andrew Gabriel [email address is not usable -- followup in the newsgroup] |