  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4
Default Vokera Boiler Issues

Hi, I have a Vokera Excel 80SP Combi Boiler which has recently been
playing up. I'm not sure if the issues below are related but I'll
include them for completeness. Any suggestions would be appreciated.

1. There is water leaking from the auto air vent. The leak only seems
to occur when the central heating is off. If I turn the thermostat up
so it's calling for heat all the time it doesn't seem to leak? I've
bled all radiators, and tried closing the cap but it still appears to
leak regardless (perhaps the cap is not sealing, but I believe it
shouldn't leak water anyway?). What would cause a leak, a broken valve
I would guess, but any other causes? I have a radiator off at the
moment for decorating but the inlet and outlet of the pipes are sealed.
I have thermostatic valves on most radiators, but there is at least
one with a "standard" valve and it is open (I know there has to be some
route to circulate water).

2. The pilot light is periodically extinguishing. The thermocouple
was replaced a few months ago during a service, so I don't believe this
to be the issue (though I guess it could be). Again if the thermostat
is turned up to call for heat constantly it doesn't extinguish (have
tried it for 2 days), but with the thermostat on normal it goes out,
usually within 24 hours. I don't think it's the recent wind either
since it has happened on calm days. Is there any way it's related to
the cause of the air vent leak issue?

3. Probably of no relevance, but I recently replace a mechanical
heating timer with a Drayton RF thermostat, so it's probably "on and
off" more regularly than normal. Like I say probably not relevant, but
mentioning it for the full picture!

I would have liked to try turning the thermostat right down to see if
any of the symptom occur when it never calls for heat, but it's just
too cold

Thanks in advance,


Simon

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 33
Default Vokera Boiler Issues

Firstly does the boiler keep losing pressure? If so when the boiler is
cold and the pressure is set to 1 bar(14psi) when it has reached temp
how high does the pressure go?, If it rises above three bar it is more
than likely the expanssion vessel. the leak on the auto air vent is
common and a cheap fix is possible.
let me know the outcome
pete
Simon wrote:
Hi, I have a Vokera Excel 80SP Combi Boiler which has recently been
playing up. I'm not sure if the issues below are related but I'll
include them for completeness. Any suggestions would be appreciated.

1. There is water leaking from the auto air vent. The leak only seems
to occur when the central heating is off. If I turn the thermostat up
so it's calling for heat all the time it doesn't seem to leak? I've
bled all radiators, and tried closing the cap but it still appears to
leak regardless (perhaps the cap is not sealing, but I believe it
shouldn't leak water anyway?). What would cause a leak, a broken valve
I would guess, but any other causes? I have a radiator off at the
moment for decorating but the inlet and outlet of the pipes are sealed.
I have thermostatic valves on most radiators, but there is at least
one with a "standard" valve and it is open (I know there has to be some
route to circulate water).

2. The pilot light is periodically extinguishing. The thermocouple
was replaced a few months ago during a service, so I don't believe this
to be the issue (though I guess it could be). Again if the thermostat
is turned up to call for heat constantly it doesn't extinguish (have
tried it for 2 days), but with the thermostat on normal it goes out,
usually within 24 hours. I don't think it's the recent wind either
since it has happened on calm days. Is there any way it's related to
the cause of the air vent leak issue?

3. Probably of no relevance, but I recently replace a mechanical
heating timer with a Drayton RF thermostat, so it's probably "on and
off" more regularly than normal. Like I say probably not relevant, but
mentioning it for the full picture!

I would have liked to try turning the thermostat right down to see if
any of the symptom occur when it never calls for heat, but it's just
too cold

Thanks in advance,


Simon


  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 4
Default Vokera Boiler Issues

It is losing pressure over time, but I'm assuming that's because of the
air vent leak, so the system is therefore not fully sealed.

I'm not aware of the pressure going high (haven't checked exactly how
high, it's in the attic so hard to get a "quick glance") but I don't
think I've ever seen it get higher than 2. There's also no evidence of
"blow off" on the overflow outside the house.

Interestingly over the weekend the boiler has been behaving, but the
pressure has been at only 0.5 bar. I don't know whether it was just
coincidence but recharging to a cold 1 bar and the pilot extinguished
twice since yesterday teatime.

In terms of the auto air vent being a cheap fix, would that be to buy
"Vokera 4254 Auto Air Vent" as listed here?

http://www.keeptheheaton.com/acatalog/Vokera_Misc.html

Thanks for your help


Simon

---

gasman pete wrote:

Firstly does the boiler keep losing pressure? If so when the boiler is
cold and the pressure is set to 1 bar(14psi) when it has reached temp
how high does the pressure go?, If it rises above three bar it is more
than likely the expanssion vessel. the leak on the auto air vent is
common and a cheap fix is possible.
let me know the outcome
pete
Simon wrote:
Hi, I have a Vokera Excel 80SP Combi Boiler which has recently been
playing up. I'm not sure if the issues below are related but I'll
include them for completeness. Any suggestions would be appreciated.

1. There is water leaking from the auto air vent. The leak only seems
to occur when the central heating is off. If I turn the thermostat up
so it's calling for heat all the time it doesn't seem to leak? I've
bled all radiators, and tried closing the cap but it still appears to
leak regardless (perhaps the cap is not sealing, but I believe it
shouldn't leak water anyway?). What would cause a leak, a broken valve
I would guess, but any other causes? I have a radiator off at the
moment for decorating but the inlet and outlet of the pipes are sealed.
I have thermostatic valves on most radiators, but there is at least
one with a "standard" valve and it is open (I know there has to be some
route to circulate water).

2. The pilot light is periodically extinguishing. The thermocouple
was replaced a few months ago during a service, so I don't believe this
to be the issue (though I guess it could be). Again if the thermostat
is turned up to call for heat constantly it doesn't extinguish (have
tried it for 2 days), but with the thermostat on normal it goes out,
usually within 24 hours. I don't think it's the recent wind either
since it has happened on calm days. Is there any way it's related to
the cause of the air vent leak issue?

3. Probably of no relevance, but I recently replace a mechanical
heating timer with a Drayton RF thermostat, so it's probably "on and
off" more regularly than normal. Like I say probably not relevant, but
mentioning it for the full picture!

I would have liked to try turning the thermostat right down to see if
any of the symptom occur when it never calls for heat, but it's just
too cold

Thanks in advance,


Simon


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
vokera combi boiler slimjim UK diy 3 October 2nd 06 07:47 PM
Vokera Linea 24 boiler Tim Steele UK diy 0 December 18th 05 10:39 PM
Vokera Excell 80 SP boiler. Neil UK diy 1 November 25th 05 07:07 PM
Vokera Linea 28 Boiler.... MrMoosehead UK diy 7 November 14th 05 12:13 AM
Ariston or Vokera boiler? stuart noble UK diy 34 June 19th 04 09:22 PM


All times are GMT +1. The time now is 02:55 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"