Home |
Search |
Today's Posts |
|
UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions. |
Reply |
|
LinkBack | Thread Tools | Display Modes |
#1
Posted to uk.d-i-y
|
|||
|
|||
Heating system's bypass valve in wrong place?
Hi. I've finally identified a strange copper pipe connection between the
flow from and return to my boiler as being a bypass circuit (with a gate valve halfway along it). From what I've read recently, bypass circuits are designed to protect the pump in case the valve is open to the central heating circuit but all the trvs have shut down. Looking at the four or five schematic diagrams that I've seen, they all have the components in the following order: Flow from boiler V Pump V Bypass circuit (back to boiler) V Valve This makes sense to me - if the valve has effectively closed, the pump can still work by sending water around the bypass circuit back to the boiler. Here's my setup - it's an open vented fully pumped system with the following bits: Flow from boiler (Potterton Suprima 60L) V Bypass circuit (back to boiler) V Pump (Grundfos Selectric) V Valve (Sundial Y-plan V4073A1039) Now, paraphrasing Snoop Doggy Dogg, "I ain't no plumber" - but this looks wrong to me. If I close the valve down completely, the pump won't be able to continue, because it's not included in the bypass circuit. Only one question for the time being: is my deduction correct? |
#2
Posted to uk.d-i-y
|
|||
|
|||
Heating system's bypass valve in wrong place?
Jaime wrote:
Hi. I've finally identified a strange copper pipe connection between the flow from and return to my boiler as being a bypass circuit (with a gate valve halfway along it). snip Here's my setup - it's an open vented fully pumped system with the following bits: Flow from boiler (Potterton Suprima 60L) V Bypass circuit (back to boiler) V Pump (Grundfos Selectric) V Valve (Sundial Y-plan V4073A1039) Now, paraphrasing Snoop Doggy Dogg, "I ain't no plumber" - but this looks wrong to me. If I close the valve down completely, the pump won't be able to continue, because it's not included in the bypass circuit. Only one question for the time being: is my deduction correct? I have not looked at the manual for the boiler. Is it possible that it's a large circuit, and the external pump is simply supplementary to the built in one? In which case of course, there is no problem. |
#3
Posted to uk.d-i-y
|
|||
|
|||
Heating system's bypass valve in wrong place?
Ian Stirling wrote:
Jaime wrote: Hi. I've finally identified a strange copper pipe connection between the flow from and return to my boiler as being a bypass circuit (with a gate valve halfway along it). snip Here's my setup - it's an open vented fully pumped system with the following bits: Flow from boiler (Potterton Suprima 60L) V Bypass circuit (back to boiler) V Pump (Grundfos Selectric) V Valve (Sundial Y-plan V4073A1039) Now, paraphrasing Snoop Doggy Dogg, "I ain't no plumber" - but this looks wrong to me. If I close the valve down completely, the pump won't be able to continue, because it's not included in the bypass circuit. Only one question for the time being: is my deduction correct? I have not looked at the manual for the boiler. Is it possible that it's a large circuit, and the external pump is simply supplementary to the built in one? In which case of course, there is no problem. I've looked at the "Installation and Service Instructions" for the Potterton Suprima 60L boiler and both of the schematic diagrams show the external pump included in the bypass circuit (i.e. flow from boiler goes to pump goes to bypass circuit goes to valve). Also, the boiler documentation says nothing about a built-in pump... |
#4
Posted to uk.d-i-y
|
|||
|
|||
Heating system's bypass valve in wrong place?
On 2006-12-09 12:23:11 +0000, Jaime said:
Hi. I've finally identified a strange copper pipe connection between the flow from and return to my boiler as being a bypass circuit (with a gate valve halfway along it). From what I've read recently, bypass circuits are designed to protect the pump in case the valve is open to the central heating circuit but all the trvs have shut down. Looking at the four or five schematic diagrams that I've seen, they all have the components in the following order: Flow from boiler V Pump V Bypass circuit (back to boiler) V Valve This makes sense to me - if the valve has effectively closed, the pump can still work by sending water around the bypass circuit back to the boiler. Here's my setup - it's an open vented fully pumped system with the following bits: Flow from boiler (Potterton Suprima 60L) V Bypass circuit (back to boiler) V Pump (Grundfos Selectric) V Valve (Sundial Y-plan V4073A1039) Now, paraphrasing Snoop Doggy Dogg, "I ain't no plumber" - but this looks wrong to me. If I close the valve down completely, the pump won't be able to continue, because it's not included in the bypass circuit. Only one question for the time being: is my deduction correct? Sounds like it, although the purpose is to keep a flow of water going through the boiler to prevent so that when the valve closes, the water doesn't become stationary and hence boil. |
#5
Posted to uk.d-i-y
|
|||
|
|||
Heating system's bypass valve in wrong place?
On Sat, 09 Dec 2006 14:12:29 +0000, Jaime wrote:
Ian Stirling wrote: Jaime wrote: Hi. I've finally identified a strange copper pipe connection between the flow from and return to my boiler as being a bypass circuit (with a gate valve halfway along it). snip Here's my setup - it's an open vented fully pumped system with the following bits: Flow from boiler (Potterton Suprima 60L) V Bypass circuit (back to boiler) V Pump (Grundfos Selectric) V Valve (Sundial Y-plan V4073A1039) Now, paraphrasing Snoop Doggy Dogg, "I ain't no plumber" - but this looks wrong to me. If I close the valve down completely, the pump won't be able to continue, because it's not included in the bypass circuit. Only one question for the time being: is my deduction correct? I have not looked at the manual for the boiler. Is it possible that it's a large circuit, and the external pump is simply supplementary to the built in one? In which case of course, there is no problem. I've looked at the "Installation and Service Instructions" for the Potterton Suprima 60L boiler and both of the schematic diagrams show the external pump included in the bypass circuit (i.e. flow from boiler goes to pump goes to bypass circuit goes to valve). Also, the boiler documentation says nothing about a built-in pump... Suprimas do not contains integral pumps the OP's set up is wrong. Depending on the nature of the bypass ('smart' valve or 'dumb' gate valve) and the nature of the rest of the heating circuit (S-plan, or Y-plan, TRVs all/none/most) you may or may not get some over-run circulation as needed. -- Ed Sirett - Property maintainer and registered gas fitter. The FAQ for uk.diy is at http://www.diyfaq.org.uk Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html Choosing a Boiler FAQ http://www.makewrite.demon.co.uk/BoilerChoice.html Gas Fitting Standards Docs he http://www.makewrite.demon.co.uk/GasFittingStandards |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
To bypass or not to bypass (UFH Central Heating) | UK diy | |||
Do I need a (differential) bypass valve? | UK diy | |||
Bypass valve position | UK diy | |||
gas grill burns in the wrong place | Home Repair | |||
ball valve in place of gate valve? | UK diy |