Running lighting cable over/through joists in loft.
The joists in my loft are less than 100mm in height, meaning that it is
impossible to drill a hole that is 50mm from both the top /and/ bottom of the joist. I've found other posts that say to run the cable over the top of the joist and have a baton either side and place steel strips over the top, e.g. http://groups.google.co.uk/group/uk....6345a2c9687a7d In parts the cable/joists will have boards over the top. Can the cable be run without earthed trunking/conduit? and does this comply with the building regs? I can't find anything which explicity covers this in the On Site Guide or the BS7671 Blue Book. |
#2
Posted to uk.d-i-y
|
|||
|
|||
Running lighting cable over/through joists in loft.
Why not drill through the joists 50mm from the bottom and put 3mm steel
plates over the top to protect from screws. I beleive this is allowed in the on site guide Regards - Lightingman |
#3
Posted to uk.d-i-y
|
|||
|
|||
Running lighting cable over/through joists in loft.
As a slight aside, given the height of the joists will I be able to run
the cables along the length/side of the joists, holding them in place with cable clips? |
#4
Posted to uk.d-i-y
|
|||
|
|||
Running lighting cable over/through joists in loft.
"thankyousam" wrote in message oups.com... As a slight aside, given the height of the joists will I be able to run the cables along the length/side of the joists, holding them in place with cable clips? This is acceptable, and is the standard way of installing Twin & Earth, PVCI cables running the length of the joists. If there is thermal insulation laid "between the joists", the cable should be run preferably, at a height corresponding to the upper surface of the insulation layer, to avoid unnecessary cable derating; but in any case, at a height of at least 50mm to the underside of the cable, measured from the bottom of the joist. (This is to avoid possible nail damage from below the ceiling). |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Raising Roof Joists for Loft Flooring | UK diy | |||
Lighting in loft conversion | UK diy | |||
Adding CH to new loft - advice please | UK diy | |||
using 30A cable to supply 5A lighting circuit: good idea? | UK diy | |||
Routeing Electrical FTE cable | UK diy |