  #1   Report Post  
Richard Faulkner
 
Posts: n/a
Default Electrical Supply to 7 Flats & Common Parts

I probably dont want to know the answer to this but, having only just
discovered it, I guess I need to know:

Big Victorian House converted many years ago into 7 flats. 7 electric
meters, common parts supplied from landlords meter.

I bought this in 2000, and managed to get rid of the final dregs of
humanity in April. 6 of the flats have now been refurbished, I live in
one of the flats, and have continued the tradition of having the common
parts fed from my meter.

However, on the basis that I wont live here forever, I want to get an
extra meter/supply for the common parts.

Anyway - in the meter cupboard, there is a very thick cable, from
outside, which feeds a panel with 3 of the big black electricity board
fuses. Tails from these 3 fuses then lead to some splitters, (???), and
tails from these splitters lead to a further 7 big black electricity
board fuses - these then feed the meters of the 7 flats.

Each flat now has Gas C/H for heating and hot water, electric oven, and
the usual lights and sockets. 5 x 1 bed flats, 1 x 2 bed flat, 1 x
studio flat.

Whilst the electricity board have always been aware that there are 7
flats, and they presumably created the layout initially, I am a bit
concerned that there should not be 7 flats fed from the 3 big fuses, and
that asking for another meter/supply may be opening a can of worms.

Any thoughts before I open the can g

Many Thanks

--
Richard Faulkner
  #2   Report Post  
BigWallop
 
Posts: n/a
Default


"Richard Faulkner" wrote in message
...
I probably dont want to know the answer to this but, having only just
discovered it, I guess I need to know:

Big Victorian House converted many years ago into 7 flats. 7 electric
meters, common parts supplied from landlords meter.

I bought this in 2000, and managed to get rid of the final dregs of
humanity in April. 6 of the flats have now been refurbished, I live in
one of the flats, and have continued the tradition of having the common
parts fed from my meter.

However, on the basis that I wont live here forever, I want to get an
extra meter/supply for the common parts.

Anyway - in the meter cupboard, there is a very thick cable, from
outside, which feeds a panel with 3 of the big black electricity board
fuses. Tails from these 3 fuses then lead to some splitters, (???), and
tails from these splitters lead to a further 7 big black electricity
board fuses - these then feed the meters of the 7 flats.

Each flat now has Gas C/H for heating and hot water, electric oven, and
the usual lights and sockets. 5 x 1 bed flats, 1 x 2 bed flat, 1 x
studio flat.

Whilst the electricity board have always been aware that there are 7
flats, and they presumably created the layout initially, I am a bit
concerned that there should not be 7 flats fed from the 3 big fuses, and
that asking for another meter/supply may be opening a can of worms.

Any thoughts before I open the can g

Many Thanks

Richard Faulkner

The layout sounds like it has a simple three phase supply, and that the
three phases have been distributed sort of evenly throughout the whole of
the flats.

If you wish to rent the flat that you currently occupy, then you could have
the landlord supply separated to a meter in the common hallway that supplies
only the stair lighting and other common parts of the building. This is a
very common layout for this type of property.

It does mean that the current supply to your flat will need to have the
common areas removed and transferred to the new meter in the hallway of
course.


  #3   Report Post  
Owain
 
Posts: n/a
Default

Richard Faulkner wrote:
Big Victorian House converted many years ago into 7 flats. 7 electric
meters, common parts supplied from landlords meter.
Whilst the electricity board have always been aware that there are 7
flats, and they presumably created the layout initially, I am a bit
concerned that there should not be 7 flats fed from the 3 big fuses, and
that asking for another meter/supply may be opening a can of worms.


There's considerable diversity applied across multiple dwellings, and
it's surprising what can be got away with. I think there are probably
closes in Scotland with a main supply of about 10A per flat :-)

I presume the landlord's supply is only for a few lights, entry system,
tv distribution, zoned fire alarm system (?) and the like. If this is
explained to the electricity co then there should be no question of
needing to upgrade the main feeder.

ScottishPower have a facility whereby landlord's meters of this type are
automatically divided and charged across tenant's electricity bills, so
you wouldn't need to read the meter and bill the tenants or absorb the
cost yourself. I don't know if other providers have the same facility or
what happens if different tenants have different leccy providers.

Owain

  #4   Report Post  
Hugh
 
Posts: n/a
Default


"Richard Faulkner" wrote in message
...
I probably dont want to know the answer to this but, having only just
discovered it, I guess I need to know:

Big Victorian House converted many years ago into 7 flats. 7 electric
meters, common parts supplied from landlords meter.

I bought this in 2000, and managed to get rid of the final dregs of
humanity in April. 6 of the flats have now been refurbished, I live in one
of the flats, and have continued the tradition of having the common parts
fed from my meter.

However, on the basis that I wont live here forever, I want to get an
extra meter/supply for the common parts.

Anyway - in the meter cupboard, there is a very thick cable, from outside,
which feeds a panel with 3 of the big black electricity board fuses. Tails
from these 3 fuses then lead to some splitters, (???), and tails from
these splitters lead to a further 7 big black electricity board fuses -
these then feed the meters of the 7 flats.

Each flat now has Gas C/H for heating and hot water, electric oven, and
the usual lights and sockets. 5 x 1 bed flats, 1 x 2 bed flat, 1 x studio
flat.

Whilst the electricity board have always been aware that there are 7
flats, and they presumably created the layout initially, I am a bit
concerned that there should not be 7 flats fed from the 3 big fuses, and
that asking for another meter/supply may be opening a can of worms.

Any thoughts before I open the can g

Many Thanks

--
Richard Faulkner


I'm sure you are aware, being a landlord, that you require each of the
dwellings to be inspected by a suitably qualified electrician and the
appropriate certificate issued. At this same time you could enquire of the
electrician whether the current (excuse pun!) layout is satisfactory - he
should be able to advise.
You can't skimp on these things tho' - you have a duty of care to your
tenants - their lives are in your hands to a certain extent - if the wiring
is unsafe it has to be updated.
Got your annual Landlord's Charter gas certs.for each flat yet. Illegal not
to when rented out.

I would be equally concerned about the imminent Housing Act 2004 regulations
coming in this autumn - this is going to affect many landlords and tenants
especially in converted flats, and properties of 3 floors or more. The cost
of works ordered by local councils will be staggering, the penalties for not
complying equally costly.

BTW, 'final dregs of humanity' ? - a lot of landlords fit that
description - and presumably you've enriched yourself by their presence in
one way or another.

Hugh


  #5   Report Post  
Lobster
 
Posts: n/a
Default

Hugh wrote:
I'm sure you are aware, being a landlord, that you require each of the
dwellings to be inspected by a suitably qualified electrician and the
appropriate certificate issued.


No you don't.

You can't skimp on these things tho' - you have a duty of care to your
tenants - their lives are in your hands to a certain extent - if the wiring
is unsafe it has to be updated.


Agree absolutely.

David


  #6   Report Post  
Hugh
 
Posts: n/a
Default


"Lobster" wrote in message
...
Hugh wrote:
I'm sure you are aware, being a landlord, that you require each of the
dwellings to be inspected by a suitably qualified electrician and the
appropriate certificate issued.


No you don't.

You can't skimp on these things tho' - you have a duty of care to your
tenants - their lives are in your hands to a certain extent - if the
wiring is unsafe it has to be updated.


Agree absolutely.

David


David,
Thanks for pointing that out - it's true that it isn't part of existing
legislation other than it must be safe. I have all my installations so
certificated, the consequences of not doing so, could be costly, to say the
least, and result in a prison sentence.
With hindsight I should have said 'should require'. I bashed-off my little
piece before dashing off to load up the car for a trip to the tip - but I
stand by the general jist of what I said.
cheers,
Hugh


  #7   Report Post  
Christian McArdle
 
Posts: n/a
Default

Anyway - in the meter cupboard, there is a very thick cable, from
outside, which feeds a panel with 3 of the big black electricity board
fuses. Tails from these 3 fuses then lead to some splitters, (???), and
tails from these splitters lead to a further 7 big black electricity
board fuses - these then feed the meters of the 7 flats.


It doesn't sound too bad if the big (i.e. 3) fuses are at least 100A.

If there's no electric heating, then in the worst case, you have 100A shared
between 3 flats. That's not the same as 33A per flat, as it is extremely
unlikely that all flats will draw maximum at all times. Also, short term
overloads are a non-issue.

In Europe, it is common for flat supplies to be limited to a low value, like
25A. I don't know the diversity calculations applicable here, but you could
use a lot more than that per flat with impunity.

Christian.


  #8   Report Post  
Chip
 
Posts: n/a
Default

On Mon, 11 Jul 2005 02:11:00 +0100,it is alleged that Richard Faulkner
spake thusly in uk.d-i-y:

[snip]

Whilst the electricity board have always been aware that there are 7
flats, and they presumably created the layout initially, I am a bit
concerned that there should not be 7 flats fed from the 3 big fuses, and
that asking for another meter/supply may be opening a can of worms.


As others have mentioned, this is quite normal in multi-occupancy
dwellings. As for 'can of worms', as others have mentioned, diversity
calculations allow this with no problems, there's also the possibility
the 3ph mainfuses might be 200A (it may be labelled on the carriers).

Also by simple mathematics, currently at least *one* of the phases has
3 flats on it, while the other phases have 2, and can thus handle an
extra each.

There should be no problem going up to 9 (with 3 on each phase) before
they start having to rethink things. And this will all be done by the
electricity supplier (being before/including the meters) so I don't
suspect the can will contain worms.

I could be wrong, but that's how it appears to me.

--
"I think computer viruses should count as life. I think it says something
about human nature that the only form of life we have created so far is
purely destructive. We've created life in our own image." - Stephen Hawking
  #9   Report Post  
Ed Sirett
 
Posts: n/a
Default

On Mon, 11 Jul 2005 02:11:00 +0100, Richard Faulkner wrote:

I probably dont want to know the answer to this but, having only just
discovered it, I guess I need to know:

Big Victorian House converted many years ago into 7 flats. 7 electric
meters, common parts supplied from landlords meter.

I bought this in 2000, and managed to get rid of the final dregs of
humanity in April. 6 of the flats have now been refurbished, I live in
one of the flats, and have continued the tradition of having the common
parts fed from my meter.

However, on the basis that I wont live here forever, I want to get an
extra meter/supply for the common parts.

Anyway - in the meter cupboard, there is a very thick cable, from
outside, which feeds a panel with 3 of the big black electricity board
fuses. Tails from these 3 fuses then lead to some splitters, (???), and
tails from these splitters lead to a further 7 big black electricity
board fuses - these then feed the meters of the 7 flats.

Each flat now has Gas C/H for heating and hot water, electric oven, and
the usual lights and sockets. 5 x 1 bed flats, 1 x 2 bed flat, 1 x
studio flat.

Whilst the electricity board have always been aware that there are 7
flats, and they presumably created the layout initially, I am a bit
concerned that there should not be 7 flats fed from the 3 big fuses, and
that asking for another meter/supply may be opening a can of worms.

Any thoughts before I open the can g

This does not sound to bad to me. I guess you will be in for the
'standard' new installation charge. The common parts need to be fed from a
new meter off one of the 'splitters' (probably a henley block) which is
currently only doing two meters. Since the original installation was sized
for electric heating albeit a while back there should be no problem like
needing to upgrade all the supply.

My guess is that 60A per flat from 100A on 3 should be adequate for a
small block of smallish flats with GCH.

--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at http://www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html


  #10   Report Post  
Richard Faulkner
 
Posts: n/a
Default

In message , Christian
McArdle writes
Anyway - in the meter cupboard, there is a very thick cable, from
outside, which feeds a panel with 3 of the big black electricity board
fuses. Tails from these 3 fuses then lead to some splitters, (???), and
tails from these splitters lead to a further 7 big black electricity
board fuses - these then feed the meters of the 7 flats.


It doesn't sound too bad if the big (i.e. 3) fuses are at least 100A.


They say 100A on them, as do the other 7 which they feed. And all are
Gas central heating and electric ovens - they have washer/dryers and
dishwashers aswell.

If there's no electric heating, then in the worst case, you have 100A shared
between 3 flats. That's not the same as 33A per flat, as it is extremely
unlikely that all flats will draw maximum at all times. Also, short term
overloads are a non-issue.


Are there any regulations which say that this is OK, or are you just
saying it's OK because it is g

In Europe, it is common for flat supplies to be limited to a low value, like
25A. I don't know the diversity calculations applicable here, but you could
use a lot more than that per flat with impunity.

Christian.



--
Richard Faulkner
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Heads up on service manuals! JW Electronics Repair 10 August 4th 04 02:53 PM
Email List For Arcade Game Parts techforce Electronics Repair 6 July 30th 04 07:37 PM
Generator Grounding PoP UK diy 10 November 13th 03 12:29 PM
Earthing Sparks UK diy 10 October 29th 03 01:27 AM
New Electrical Regs PoP UK diy 22 September 1st 03 08:41 PM


All times are GMT +1. The time now is 12:15 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"