Hi, I'm redesigning my central heating, changing from an old oil boiler to
gas and installing a new HWT.

Currently, the boiler is at one end of my long end semi. The pipes split
next to the boiler, one set going upstairs and travelling to the front of
the house to serve the upstairs rads, and the same downstairs.

I would like to move the HWT to the landing in the middle of the house
with the boiler above it in the attic (changing to fully pumped).

My question is;
With this arrangement the pipe from the boiler will split for upstairs
and downstairs rads, but instead of being a straight run they will both
have T-pieces near the boiler for the pipes runs to the rads at the front
and rear of the house. Will this work and be efficient.

Thank you,

Neil

  #2   Report Post  
Christian McArdle
 
Posts: n/a
Default Central heating layout design

With this arrangement the pipe from the boiler will split
for upstairs and downstairs rads, but instead of being a
straight run they will both have T-pieces near the boiler
for the pipes runs to the rads at the front and rear of
the house. Will this work and be efficient.


Yes. As the splits will be near the boiler, take the time to install 2 port
valves for the upstairs and downstairs circuits and run on a Honeywell 'S'
plan. This way, you can have a seperate programmer and room thermostat for
each floor, meaning you don't wastefully heat your bedrooms during the day.

As you have additional splits for the front and rear, you could even put
valves on these, giving four zones for even better control. It would depend
on exactly which rooms were served to decide if this would be beneficial.

Ensure every room with a wall thermostat doesn't have a TRV on the
radiators. You'll need to balance the system properly, ensuring that rooms
with TRVs heat up quicker than rooms with wall thermostats. This will ensure
that the boiler and zone valve is not turned off when TRVed rooms still need
heat.

Christian.


  #3   Report Post  
Andy Hall
 
Posts: n/a
Default Central heating layout design

On Mon, 11 Aug 2003 09:03:58 +0000 (UTC), (Niel
A. Farrow) wrote:

Hi, I'm redesigning my central heating, changing from an old oil boiler to
gas and installing a new HWT.

Currently, the boiler is at one end of my long end semi. The pipes split
next to the boiler, one set going upstairs and travelling to the front of
the house to serve the upstairs rads, and the same downstairs.

I would like to move the HWT to the landing in the middle of the house
with the boiler above it in the attic (changing to fully pumped).

My question is;
With this arrangement the pipe from the boiler will split for upstairs
and downstairs rads, but instead of being a straight run they will both
have T-pieces near the boiler for the pipes runs to the rads at the front
and rear of the house. Will this work and be efficient.

Thank you,

Neil


I had a very similar issue, Neil.

It will certainly work and there are a few things that you can do to
improve the flow conditions.

- If possible, and the fittings allow, do the connections to the
boiler in 28mm rather than 22mm.

- It is best to make swept bends with a pipe bender to reduce the
resistance. If you don't have a bender for 28mm, a good substitute
is to use two obtuse bends with a short length of pipe between them.

- For the tees I used 28mm types which instead of being completely
angular are made with a swept bend each way. I then ran about a
metre of 28mm pipe on each leg before reducing down to 22mm.
I used 28mm zone valves.

The key thing is to avoid using sharp bends wherever you can.
If you have a choice of pump, a Grundfos Alpha is useful because it
has adjustment but also adjusts output automatically to the pressure
resistance

..andy

To email, substitute .nospam with .gl
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Central heating Q Mungo \two sheds\ Toadfoot UK diy 28 February 11th 05 11:08 AM
2 port Vs 3 port central heating valves EMC UK diy 16 July 31st 03 08:09 PM
Further to my last post entitled 'Flushing and treating central heating question' David W.E. Roberts UK diy 0 July 29th 03 07:15 PM
Dataterm IHC vs Danfoss TP75 Central Heating controllers Matt UK diy 0 July 28th 03 08:41 AM
Costs for Gas Central heating from Electric storage Richard Markham UK diy 0 July 14th 03 08:46 PM


All times are GMT +1. The time now is 09:42 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"