Default Wiring Up Cabinet Halogens

As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. These are full 110v
lamps, not 12v bulbs with a transformer. I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.

These lights are wired with 18g "lamp cord". Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? I have not yet installed
the drywall and have full access to the studs. As long as the
connections end in a standard box, is there a problem?

--Jeff
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,563
Default Wiring Up Cabinet Halogens

Yes, it is a code violation to run lamp cord through partitions and inside
walls. The proper thing to do is install a switched outlet inside the
cabinet, then plug the lights in.
"Jeff B" wrote in message
...
As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. These are full 110v
lamps, not 12v bulbs with a transformer. I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.

These lights are wired with 18g "lamp cord". Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? I have not yet installed
the drywall and have full access to the studs. As long as the
connections end in a standard box, is there a problem?

--Jeff



  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default Wiring Up Cabinet Halogens


"Jeff B" wrote in message
...
As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. These are full 110v
lamps, not 12v bulbs with a transformer. I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.

These lights are wired with 18g "lamp cord". Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? I have not yet installed
the drywall and have full access to the studs. As long as the
connections end in a standard box, is there a problem?




Yes it's a problem. Lamp cord is not rated for in wall use. The long term
ramification is that the insulation will dry up, become brittle, and break
off. An acceptable alternative would be to install switched receptacles
above the cabinets and just plug the lights in. Put your switch where ever
you want it using regular Romex or BX wiring and the appropriate electrical
boxes. If the cabinets go up to the ceiling, mount adjustable depth boxes
in the wall and cut holes in the back of the cabinets around the boxes.
That way you will have receptacles flush inside of the cabinets.

  #4   Report Post  
Posted to alt.home.repair
Joe Joe is offline
external usenet poster
 
Posts: 2,837
Default Wiring Up Cabinet Halogens



Jeff B wrote:
As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. These are full 110v
lamps, not 12v bulbs with a transformer. I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.


Are your cabinets flush to the ceiling? If not, isn't there room there
for a switched outlet?

Joe
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 455
Default Wiring Up Cabinet Halogens

Jeff B wrote:

As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. These are full 110v
lamps, not 12v bulbs with a transformer. I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.

These lights are wired with 18g "lamp cord". Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? I have not yet installed
the drywall and have full access to the studs. As long as the
connections end in a standard box, is there a problem?


Yes. Romex is designed to keep an overheated wire contained and minimize the
chance of an inwall fire. Running zip cord through a wall is a really dumb idea
- especially as you have access to the inside of the wall. Run Romex to an
outlet above the cabinet(s).


  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 34
Default Wiring Up Cabinet Halogens

On Jan 4, 7:50*pm, "John Grabowski" wrote:
"Jeff B" wrote in message

...

As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. *These are full 110v
lamps, not 12v bulbs with a transformer. *I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.


These lights are wired with 18g "lamp cord". *Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? *I have not yet installed
the drywall and have full access to the studs. *As long as the
connections end in a standard box, is there a problem?


Yes it's a problem. *Lamp cord is not rated for in wall use. *The long term
ramification is that the insulation will dry up, become brittle, and break
off. *An acceptable alternative would be to install switched receptacles
above the cabinets and just plug the lights in. *Put your switch where ever
you want it using regular Romex or BX wiring and the appropriate electrical
boxes. *If the cabinets go up to the ceiling, mount adjustable depth boxes
in the wall and cut holes in the back of the cabinets around the boxes.
That way you will have receptacles flush inside of the cabinets.


THanks for all of the responses. Back to the drawing paper.

My cabs end 6" below ceiling height but the gap will be closed off
with crown molding. This means I can't put a switched outlet in that
space...unless I make an "access panel" in the molding...which I don't
want to do. It sounds like a switched outlet INSIDE each glass cab is
my only option?

--Jeff
  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 663
Default Wiring Up Cabinet Halogens

On Fri, 4 Jan 2008 17:51:23 -0800 (PST), Jeff B
wrote:

On Jan 4, 7:50*pm, "John Grabowski" wrote:
"Jeff B" wrote in message

...

As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. *These are full 110v
lamps, not 12v bulbs with a transformer. *I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.


These lights are wired with 18g "lamp cord". *Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? *I have not yet installed
the drywall and have full access to the studs. *As long as the
connections end in a standard box, is there a problem?


Yes it's a problem. *Lamp cord is not rated for in wall use. *The long term
ramification is that the insulation will dry up, become brittle, and break
off. *An acceptable alternative would be to install switched receptacles
above the cabinets and just plug the lights in. *Put your switch where ever
you want it using regular Romex or BX wiring and the appropriate electrical
boxes. *If the cabinets go up to the ceiling, mount adjustable depth boxes
in the wall and cut holes in the back of the cabinets around the boxes.
That way you will have receptacles flush inside of the cabinets.


THanks for all of the responses. Back to the drawing paper.

My cabs end 6" below ceiling height but the gap will be closed off
with crown molding. This means I can't put a switched outlet in that
space...unless I make an "access panel" in the molding...which I don't
want to do. It sounds like a switched outlet INSIDE each glass cab is
my only option?

--Jeff


You might be able to rewire them with romex.
  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,199
Default Wiring Up Cabinet Halogens

On Jan 4, 6:59*pm, Jeff B wrote:
As part of my kitchen remodeling project, I am planning on installing
"hockey puck" halogens inside the tops of 3 of the wall cabinets that
have glass doors and glass shelves for display. *These are full 110v
lamps, not 12v bulbs with a transformer. *I do NOT want to run the
wires thru the bottom of the cab and plug them into an outlet...I
wanted to have them switched thru a normal wall box and light
switch.

These lights are wired with 18g "lamp cord". *Is there any code reason
why I can't run it behind the drywall and into the switch box (of
course running it thru studs like romex)? *I have not yet installed
the drywall and have full access to the studs. *As long as the
connections end in a standard box, is there a problem?

--Jeff


Hey Jeff. My cabinets did not go up to the ceiling, so I was able to
install an outlet above the cabinet, but since you are going to the
ceiling obviously that is not an option, but keep in mind the
manufacturers of these lights do not recommend recessing the light in
an enclosed space, so I don't know if the enclosed space above your
cabinets would be the same thing. These lights get hot and need to
dissipate the heat in open air. Even if you surface mount the lights
instead of recessing them, it would be inside a closed cabinet and
thus cannot dissipate heat.
My undercounter lights are surface mounted and believe me, they do
generate a bit of heat. Check some lighting stores and see if they
sell a recessed light that is approved for enclosed spaces.
As for where to put the outlet, could you not put an outlet in
adjacent cabinet with no glass doors this way you would not see it?
Also, is is it possible to make a change and not go up to the ceiling
with crown and leave about 3-4" space?
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Wiring and plug for a 3 hp cabinet saw David Todtman Woodworking 48 October 16th 07 02:00 PM
LV Halogens elziko UK diy 17 September 10th 07 03:38 PM
wiring under cabinet lighting to combination switch [email protected] Home Repair 4 June 8th 06 01:22 PM
Electrical - Wiring a pendant light from a cabinet valence [email protected] Home Ownership 2 January 5th 06 05:23 PM
Kitchen Cabinet + Downlights Wiring ANt UK diy 7 January 3rd 04 09:30 AM


All times are GMT +1. The time now is 04:16 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"