Default Ultra Boiler Modulation

Hello,

I am the proud owner of a Weil Maclean Ultra 105 boiler; it was
insalled this past May. Generally, I like the unit, but I am confused
about modulation: The literature says it has "20-100% modulation."
Does that mean it fires at any rate between those two? Or at JUST 20%
and 100%?

Thanks,

Mike


----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----
http://www.newsfeeds.com The #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 5,823
Default Ultra Boiler Modulation


"Michael Gallagher" wrote in message
...
Hello,

I am the proud owner of a Weil Maclean Ultra 105 boiler; it was
insalled this past May. Generally, I like the unit, but I am confused
about modulation: The literature says it has "20-100% modulation."
Does that mean it fires at any rate between those two? Or at JUST 20%
and 100%?

Thanks,

Mike


Any modulating boiler I'm familiar with is a variable firing rate. The W-M
uses a mixing venturi to send the gas/air mix to the burner with a 5 - 1
turndown ratio


  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4
Default Ultra Boiler Modulation

On Sat, 16 Dec 2006 00:07:31 GMT, "Edwin Pawlowski"
wrote:


Any modulating boiler I'm familiar with is a variable firing rate. The W-M
uses a mixing venturi to send the gas/air mix to the burner with a 5 - 1
turndown ratio


So for clarification, bearing in mind I am not up on the terminology,
you are saying it can fire anywhere between 20% and 100% inclusive?



----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----
http://www.newsfeeds.com The #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----
  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 5,823
Default Ultra Boiler Modulation


"Michael Gallagher" wrote in message

So for clarification, bearing in mind I am not up on the terminology,
you are saying it can fire anywhere between 20% and 100% inclusive?


Yes. Most of this type of boiler senses the temperature and will trim the
fire to maintain a steady water temperature as opposed to the older methods
of turning the burner off, starting it back up again when the temperature
comes down, shutting off again, and repeating.

I don't know the exact setup WM uses, but let's say the maximum temperature
is going to be 185 degrees. At about 180, it may go down to 20% fire and
let it creep up slowly. On a very cold day, the water coming back to the
boiler may be 120 degrees and that will cause the burner to go back up to
100% until it reaches a warm enough water temp to start backing down. The
result is more even heating, less temperature swings.


  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4
Default Ultra Boiler Modulation

On Sat, 16 Dec 2006 14:04:56 -0500, "Edwin Pawlowski"
wrote:


"Michael Gallagher" wrote in message

So for clarification, bearing in mind I am not up on the terminology,
you are saying it can fire anywhere between 20% and 100% inclusive?


Yes. Most of this type of boiler senses the temperature and will trim the
fire to maintain a steady water temperature as opposed to the older methods
of turning the burner off, starting it back up again when the temperature
comes down, shutting off again, and repeating.

I don't know the exact setup WM uses, but let's say the maximum temperature
is going to be 185 degrees. At about 180, it may go down to 20% fire and
let it creep up slowly. On a very cold day, the water coming back to the
boiler may be 120 degrees and that will cause the burner to go back up to
100% until it reaches a warm enough water temp to start backing down. The
result is more even heating, less temperature swings.


Thanks for the clarification; I have a better idea of what's going on.



----== Posted via Newsfeeds.Com - Unlimited-Unrestricted-Secure Usenet News==----
http://www.newsfeeds.com The #1 Newsgroup Service in the World! 120,000+ Newsgroups
----= East and West-Coast Server Farms - Total Privacy via Encryption =----
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Ultra Boiler and 60s Outside Temps Michael Gallagher Home Repair 0 May 30th 06 06:43 PM
AM modulation index John Fields Electronics 0 March 22nd 06 08:57 PM
Weil-McLain Ultra Boiler Michael Gallagher Home Repair 6 January 30th 06 05:34 PM
AM modulation monitor Reed Park Electronics Repair 11 December 11th 04 12:13 AM
Weil-Mclain Ultra Boiler? Any Good? HeatMan Home Repair 1 July 28th 04 12:38 PM


All times are GMT +1. The time now is 03:42 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"