Default New furnace hums

Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.
  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 625
Default New furnace hums

I've owned a couple Heil furnaces, 92% natural gas forced air, and both have
a small but detectable hum from the transformer. In both cases (the Heil I
installed 19 years ago and the Heil I installed last winter) the hum was
really only noticeable if you got up close to the cabinet.

Smarty


"Puddin' Man" wrote in message
...
Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.



  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 58
Default New furnace hums


Puddin' Man wrote:
With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.


Same with my year-old Lennox. Audible for a few feet.

  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 96
Default New furnace hums

On Sun, 5 Nov 2006 15:47:52 -0500, "Smarty" wrote:

I've owned a couple Heil furnaces, 92% natural gas forced air, and both have
a small but detectable hum from the transformer. In both cases (the Heil I
installed 19 years ago and the Heil I installed last winter) the hum was
really only noticeable if you got up close to the cabinet.


Thanks.

Damned if I remember a hum from the Carrier (actually a
Bryant) that we ripped out of her last spring. And I
was in the cabinet workin' on it a couple times in
it's last (20th) year.

Hope you've had good service from both Heil units.

Puddin'



"Puddin' Man" wrote in message
.. .
Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.



Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,743
Default New furnace hums


"Puddin' Man" wrote in message
...
Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.


It doesn't know the words?




  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 625
Default New furnace hums

I had superb service from my first Heil, which was one of the very first 92%
furnaces offered 20 years ago when I installed it. The new Heil was put in
last year to avoid surprising repairs or failures when I am out of town
traveling (I am now retired) and I just hope it will be as good as the last
Heil. It seems more complex and thus more likely to fail, something I was
disappointed to see. I bought a 2 stage unit hoping to save some fuel and
electric costs, but this has not proved to be the case, so I wind up with
more complexity and no apparent savings. It does run quieter however, since
it is mostly on the lower speed blower and lower output burner stage. The
new igniter system is my biggest concern.

The hum in both of my units is really not a big deal. I can not hear it
elsewhere in the house. There may be a way to get the hum reduced in yours
if it is really objectionable. Either replace the transformer, or put it on
vibration isolators of some type (rubber grommets or some spacers to isolate
the noise from getting into the furnace cabinet).

Smarty

"Puddin' Man" wrote in message
...
On Sun, 5 Nov 2006 15:47:52 -0500, "Smarty" wrote:

I've owned a couple Heil furnaces, 92% natural gas forced air, and both
have
a small but detectable hum from the transformer. In both cases (the Heil I
installed 19 years ago and the Heil I installed last winter) the hum was
really only noticeable if you got up close to the cabinet.


Thanks.

Damned if I remember a hum from the Carrier (actually a
Bryant) that we ripped out of her last spring. And I
was in the cabinet workin' on it a couple times in
it's last (20th) year.

Hope you've had good service from both Heil units.

Puddin'



"Puddin' Man" wrote in message
. ..
Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.



Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.



  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 96
Default New furnace hums

On Mon, 6 Nov 2006 08:15:13 -0500, "Smarty" wrote:

I had superb service from my first Heil, which was one of the very first 92%
furnaces offered 20 years ago when I installed it. The new Heil was put in
last year to avoid surprising repairs or failures when I am out of town
traveling (I am now retired) and I just hope it will be as good as the last
Heil. It seems more complex and thus more likely to fail, something I was
disappointed to see. I bought a 2 stage unit hoping to save some fuel and
electric costs, but this has not proved to be the case, so I wind up with
more complexity and no apparent savings.


Part of what I had to size up when I spec'd my mew unit.
I got single stage.

It does run quieter however, since
it is mostly on the lower speed blower and lower output burner stage. The


Mine is noisy, but it doesn't much bother me (yet).

new igniter system is my biggest concern.


I gotta extra glow plug outa the contractor.

The hum in both of my units is really not a big deal. I can not hear it
elsewhere in the house. There may be a way to get the hum reduced in yours
if it is really objectionable. Either replace the transformer, or put it on
vibration isolators of some type (rubber grommets or some spacers to isolate
the noise from getting into the furnace cabinet).


The only reason it bothered me was, I didn't know if it
was normal, and I needed to find out well before the
warranty expired. Issue resolved.

Thanks,
Puddin'


"Puddin' Man" wrote in message
.. .
On Sun, 5 Nov 2006 15:47:52 -0500, "Smarty" wrote:

I've owned a couple Heil furnaces, 92% natural gas forced air, and both
have
a small but detectable hum from the transformer. In both cases (the Heil I
installed 19 years ago and the Heil I installed last winter) the hum was
really only noticeable if you got up close to the cabinet.


Thanks.

Damned if I remember a hum from the Carrier (actually a
Bryant) that we ripped out of her last spring. And I
was in the cabinet workin' on it a couple times in
it's last (20th) year.

Hope you've had good service from both Heil units.

Puddin'



"Puddin' Man" wrote in message
...
Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.


Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.



Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old ...
  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 625
Default New furnace hums

Glad to help.


"Puddin' Man" wrote in message
...
On Mon, 6 Nov 2006 08:15:13 -0500, "Smarty" wrote:

I had superb service from my first Heil, which was one of the very first
92%
furnaces offered 20 years ago when I installed it. The new Heil was put in
last year to avoid surprising repairs or failures when I am out of town
traveling (I am now retired) and I just hope it will be as good as the
last
Heil. It seems more complex and thus more likely to fail, something I was
disappointed to see. I bought a 2 stage unit hoping to save some fuel and
electric costs, but this has not proved to be the case, so I wind up with
more complexity and no apparent savings.


Part of what I had to size up when I spec'd my mew unit.
I got single stage.

It does run quieter however, since
it is mostly on the lower speed blower and lower output burner stage. The


Mine is noisy, but it doesn't much bother me (yet).

new igniter system is my biggest concern.


I gotta extra glow plug outa the contractor.

The hum in both of my units is really not a big deal. I can not hear it
elsewhere in the house. There may be a way to get the hum reduced in yours
if it is really objectionable. Either replace the transformer, or put it
on
vibration isolators of some type (rubber grommets or some spacers to
isolate
the noise from getting into the furnace cabinet).


The only reason it bothered me was, I didn't know if it
was normal, and I needed to find out well before the
warranty expired. Issue resolved.

Thanks,
Puddin'


"Puddin' Man" wrote in message
. ..
On Sun, 5 Nov 2006 15:47:52 -0500, "Smarty" wrote:

I've owned a couple Heil furnaces, 92% natural gas forced air, and both
have
a small but detectable hum from the transformer. In both cases (the Heil
I
installed 19 years ago and the Heil I installed last winter) the hum was
really only noticeable if you got up close to the cabinet.

Thanks.

Damned if I remember a hum from the Carrier (actually a
Bryant) that we ripped out of her last spring. And I
was in the cabinet workin' on it a couple times in
it's last (20th) year.

Hope you've had good service from both Heil units.

Puddin'



"Puddin' Man" wrote in message
m...
Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.


Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old.



Pease pudding hot,
Pease pudding cold,
Pease pudding in the pot
Nine days old ...



  #9   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 3,515
Default New furnace hums

Puddin' Man posted for all of us...

Hi,

I got a new Heil (ICP) furnace for my little brick
bungalow last spring. Heats OK (so far).

With Tstat calling for inaction, it sits there and hums.
I flip the shutoff switch and the hum dies.

Gotta be the transformer? I don't recall a transformer
hum with previous furnaces.

Is this normal? Doe it make a difference if the
transformer is Honeywell?

Thx,
Puddin'

Asked and answered MANY times - do your own research.

--
Tekkie Don't bother to thank me, I do this as a public service.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Blower on furnace hums and doesn't start Mark Home Repair 87 February 18th 18 04:21 AM
Purchasing Furnace - 2-Stage Variable vs. Standard pipco Home Repair 21 January 27th 06 01:48 PM
Help. Furnace improperly installed? Chuck Home Repair 11 November 2nd 04 02:26 AM
Clueless Inspector Faults Furnace Install Hell Toupee Home Repair 3 October 8th 04 06:47 PM
Furnace problems - repair, replace or ???? Paul Home Repair 11 March 24th 04 12:59 AM


All times are GMT +1. The time now is 02:45 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"