Default Blades -- A home repair mystery -- ceiling fans

It was a dark and muggy night. I was working late and got home to a home
full of thick damp July night air. I switched on a ceiling fan, but it just
stood there, as still and quiet as the soggy bleakness of the Midwest
summer. "Hmmph. Another broken ceiling fan." You see, in this house there
are only seven ceiling fans, and more than half of them have met an untimely
death in the last year. I can't say for sure that this is a serial killing,
and autopsies are hard to come by, but here's the facts about the ceiling
fans: the master bedroom, the kitchen and the den have the three working
ones; the gazebo, the entryway, and the other two bedrooms have the four
that have failed this year. I'm no 60 cycle gumshoe, I prefer the safety and
comfort of digital logic, but I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no effect.
A check of the neighborhood revealed hotness on the wall switches leading to
the fans. Is my luck really that bad? What do these poor victims have in
common, other than they are fans? I needed answers like I needed air
movement. Could some sort of electrical tsunami simple wash upon my shores
and vanish, laying waste to these hearty induction motors whilst sparing all
my more delicate and expensive electronics? "Well, maybe I'm not so unlucky
after all," I mumbled out loud. Could it be that a house would be wired with
four ceiling fans, sort of scattered around the house, on a common circuit?
Could it be that this circuit has suddenly failed in a way that didn't
merely trip the breaker? Could it really be that one of these failed ceiling
fans has a separate circuit for its attached lighting? A problem as sticky
as the heavy motionless mass fogging up my glasses, a problem for the fine
folks at ahr to help me out with.
-LZ



  #2   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 68
Default Blades -- A home repair mystery -- ceiling fans

Well written.

Thank you.

I wish I had some idea of a diagnosis or cure to offer you.

You have earned it.

--
Jim McLaughlin

Reply address is deliberately munged.
If you really need to reply directly, try:
jimdotmclaughlinatcomcastdotcom

And you know it is a dotnet not a dotcom
address.
"Lou Zher" wrote in message
...
It was a dark and muggy night. I was working late and got home to a home
full of thick damp July night air. I switched on a ceiling fan, but it

just
stood there, as still and quiet as the soggy bleakness of the Midwest
summer. "Hmmph. Another broken ceiling fan." You see, in this house there
are only seven ceiling fans, and more than half of them have met an

untimely
death in the last year. I can't say for sure that this is a serial

killing,
and autopsies are hard to come by, but here's the facts about the ceiling
fans: the master bedroom, the kitchen and the den have the three working
ones; the gazebo, the entryway, and the other two bedrooms have the four
that have failed this year. I'm no 60 cycle gumshoe, I prefer the safety

and
comfort of digital logic, but I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no

effect.
A check of the neighborhood revealed hotness on the wall switches leading

to
the fans. Is my luck really that bad? What do these poor victims have in
common, other than they are fans? I needed answers like I needed air
movement. Could some sort of electrical tsunami simple wash upon my shores
and vanish, laying waste to these hearty induction motors whilst sparing

all
my more delicate and expensive electronics? "Well, maybe I'm not so

unlucky
after all," I mumbled out loud. Could it be that a house would be wired

with
four ceiling fans, sort of scattered around the house, on a common

circuit?
Could it be that this circuit has suddenly failed in a way that didn't
merely trip the breaker? Could it really be that one of these failed

ceiling
fans has a separate circuit for its attached lighting? A problem as sticky
as the heavy motionless mass fogging up my glasses, a problem for the fine
folks at ahr to help me out with.
-LZ





  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 14
Default Blades -- A home repair mystery -- ceiling fans

Is it possible that there is a second switch on each of the fans that
controls speed?
Perhaps a pull chain that goes off, low, medium, high?
And that someone turned them off?
Are the wall switches simple on-off toggles or are they speed controls?


Lou Zher wrote:
It was a dark and muggy night. I was working late and got home to a home
full of thick damp July night air. I switched on a ceiling fan, but it just
stood there, as still and quiet as the soggy bleakness of the Midwest
summer. "Hmmph. Another broken ceiling fan." You see, in this house there
are only seven ceiling fans, and more than half of them have met an untimely
death in the last year. I can't say for sure that this is a serial killing,
and autopsies are hard to come by, but here's the facts about the ceiling
fans: the master bedroom, the kitchen and the den have the three working
ones; the gazebo, the entryway, and the other two bedrooms have the four
that have failed this year. I'm no 60 cycle gumshoe, I prefer the safety and
comfort of digital logic, but I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no effect.
A check of the neighborhood revealed hotness on the wall switches leading to
the fans. Is my luck really that bad? What do these poor victims have in
common, other than they are fans? I needed answers like I needed air
movement. Could some sort of electrical tsunami simple wash upon my shores
and vanish, laying waste to these hearty induction motors whilst sparing all
my more delicate and expensive electronics? "Well, maybe I'm not so unlucky
after all," I mumbled out loud. Could it be that a house would be wired with
four ceiling fans, sort of scattered around the house, on a common circuit?
Could it be that this circuit has suddenly failed in a way that didn't
merely trip the breaker? Could it really be that one of these failed ceiling
fans has a separate circuit for its attached lighting? A problem as sticky
as the heavy motionless mass fogging up my glasses, a problem for the fine
folks at ahr to help me out with.
-LZ


  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 831
Default Blades -- A home repair mystery -- ceiling fans


Lou Zher wrote:
It was a dark and muggy night. I was working late and got home to a home
full of thick damp July night air. I switched on a ceiling fan, but it just
stood there, as still and quiet as the soggy bleakness of the Midwest
summer. "Hmmph. Another broken ceiling fan." You see, in this house there
are only seven ceiling fans, and more than half of them have met an untimely
death in the last year. I can't say for sure that this is a serial killing,
and autopsies are hard to come by, but here's the facts about the ceiling
fans: the master bedroom, the kitchen and the den have the three working
ones; the gazebo, the entryway, and the other two bedrooms have the four
that have failed this year. I'm no 60 cycle gumshoe, I prefer the safety and
comfort of digital logic, but I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no effect.
A check of the neighborhood revealed hotness on the wall switches leading to
the fans. Is my luck really that bad? What do these poor victims have in
common, other than they are fans? I needed answers like I needed air
movement. Could some sort of electrical tsunami simple wash upon my shores
and vanish, laying waste to these hearty induction motors whilst sparing all
my more delicate and expensive electronics? "Well, maybe I'm not so unlucky
after all," I mumbled out loud. Could it be that a house would be wired with
four ceiling fans, sort of scattered around the house, on a common circuit?
Could it be that this circuit has suddenly failed in a way that didn't
merely trip the breaker? Could it really be that one of these failed ceiling
fans has a separate circuit for its attached lighting? A problem as sticky
as the heavy motionless mass fogging up my glasses, a problem for the fine
folks at ahr to help me out with.
-LZ


Nice post.

Hotness on the switches leading to the fans? Dimmer switches? First
thing I would check is the speed setting (3 way pull chain) on the
fan's motor. If you have anything other than a standard toggle switch
on the wall the fan needs to always be on hi-speed. Some fans are not
compatible with dimmer switches no matter what setting they are on.
Last house I had the previous owner had installed dimmers on all of the
fans causing the motors to hum (not good for motors). Changed to
regular on/off switches and the motors ran fine with no humming.

If the above is not the case check the voltage at a few outlets
throughout the house. Motors are designed to run at a specific voltage
and behave badly when they don't get what they want. Transformers on
the pole do go bad and electric lights will work fine but motors and
electronics can suffer damage. Anything else in the house behaving
poorly like a microwave? Tough to tell without taking the cover off of
the electrical panel but were/are all the bad fans on the same leg of
the electrical service?

  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,300
Default Blades -- A home repair mystery -- ceiling fans

Lou Zher wrote:

snipped
I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no effect.
A check of the neighborhood revealed hotness on the wall switches leading to
the fans.



Questions:

1. When you say "hotness" I presume you're trying to sound like you're
"one of the boys" and are using that term to mean VOLTAGE. If not, and
you really meant that the wall switches are all thermally HOT, then pull
the main breaker move everyone out of the place and get a pro there fast!

2. What did you measure that "hotness" with? If it was a digital
multimeter, you may have been fooled by capacitive coupling allowing
just enough nanoamps through to give you a meter reading, without any
real current capability beyond that. If you're a digital guy you oughta
know, digital stuff can run on microamps, fans take AMPS. You may have
an open connection on the 120 volt (black) wire somewhere ahead of those
switches and the meter is fooling you by reading a 'phantom' voltage.

3. What did you measure that "hotness" with respect to. If it was
ground, and not the neutral return, you may have an open neutral
connection somewhere.

Best to use a light bulb to see if you've really got power available
between the output terminal of one of those fan switches and the neutral
(white) wire going up to the fan.

4. Did you ever learn what paragraph breaks are?

HTH,

Jeff










--
Jeffry Wisnia
(W1BSV + Brass Rat '57 EE)
"Rudeness is the weak man's imitation of strength."


  #6   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,743
Default Blades -- A home repair mystery -- ceiling fans

Jeff Wisnia wrote:
Lou Zher wrote:

snipped
I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no
effect. A check of the neighborhood revealed hotness on the wall
switches leading to the fans.



Questions:

1. When you say "hotness" I presume you're trying to sound like you're
"one of the boys" and are using that term to mean VOLTAGE. If not, and
you really meant that the wall switches are all thermally HOT, then
pull the main breaker move everyone out of the place and get a pro there
fast!


[...]

No, it could have been the relative quality of his housemate who was helping
with the project.


  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 2
Default Blades -- A home repair mystery -- ceiling fans

Yes, I measured w/ a DVM, but I can tell the diff between a floater and a
solid 120. I measured against a nearby wall outlet's return 'cause the wall
switch is hot-side only. You nailed it. I have an open return which is why
three of the four don't work. Something I couldn't tell until I got upon a
ladder, dropped the canopy and spun off the nuts. The fourth fan, the one
with the light fixture, is fried.
TFTH
-LZ

"Jeff Wisnia" wrote in message
et...
Lou Zher wrote:

snipped
I did try rebooting the house, one
circuit-breaker at a time and hunting down all the GFCI resets... no
effect. A check of the neighborhood revealed hotness on the wall switches
leading to the fans.



Questions:

1. When you say "hotness" I presume you're trying to sound like you're
"one of the boys" and are using that term to mean VOLTAGE. If not, and you
really meant that the wall switches are all thermally HOT, then pull the
main breaker move everyone out of the place and get a pro there fast!

2. What did you measure that "hotness" with? If it was a digital
multimeter, you may have been fooled by capacitive coupling allowing just
enough nanoamps through to give you a meter reading, without any real
current capability beyond that. If you're a digital guy you oughta know,
digital stuff can run on microamps, fans take AMPS. You may have an open
connection on the 120 volt (black) wire somewhere ahead of those switches
and the meter is fooling you by reading a 'phantom' voltage.

3. What did you measure that "hotness" with respect to. If it was ground,
and not the neutral return, you may have an open neutral connection
somewhere.

Best to use a light bulb to see if you've really got power available
between the output terminal of one of those fan switches and the neutral
(white) wire going up to the fan.

4. Did you ever learn what paragraph breaks are?

HTH,

Jeff










--
Jeffry Wisnia
(W1BSV + Brass Rat '57 EE)
"Rudeness is the weak man's imitation of strength."



Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
how to repair pop-corn acoustic ceiling? 2006 August Home Repair 15 August 15th 06 01:21 AM
GE refrigerator warranty repair misery [email protected] Home Ownership 6 March 13th 05 04:29 AM
Home Inspection Careers A-Pro Home Inspection Home Repair 1 November 26th 04 11:49 AM
Rolled Roofing Blowing Off Manufactured Home, Repair Expensive? AJ Home Ownership 5 July 9th 03 12:12 AM
Is this Home Repair or not Joseph Meehan Home Repair 12 June 28th 03 10:27 PM


All times are GMT +1. The time now is 01:37 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"