Default Whole wall as duct

I've been doing a lot of poking around in my recently purchased house
in preparation for some major wiring work (the house has the original
1948 wiring, and I'm going to be adding a lot of up-to-code circuits).
The house is a 1.5 story with a finished attic. When I took off one of
the floor heating vents in the attic (forced-air heat) and shone a
light down the opening, I discovered quite a bit of electrical wiring,
including a junction box, visible below. As far as I can tell, attached
to the box is a wall light fixture in a room on the main floor.

I haven't done a lot of further investigating yet (I didn't have a
powerful enough flashlight), but it looks like it might be the case
that the ducting is not continuous from the basement to the upper floor
- the whole section of wall between the two joists is being used as the
duct. This is obviously very bad - especially considering the
electrical wiring in the space. I'm planning to replace the wiring
anyways, so it won't be a problem, but I should do something about the
duct. What options, short of ripping up a section of wall on the main
floor, do I have? My fiancee is not going to be happy if I tell her
that we have to rip out a section of wall, though if that's the only
option, I guess I'll do it (at least that wall only has paneling, not
drywall).

It looks like the wiring is original, so that means that either someone
was careless at the time of construction, or some HVAC person did a
crappy job when adding a vent to the upstairs.

Any tips on how I should handle this? Thanks in advance.

  #2   Report Post  
Posted to alt.home.repair
Doug Kanter
 
Posts: n/a
Default Whole wall as duct

wrote in message
oups.com...
I've been doing a lot of poking around in my recently purchased house
in preparation for some major wiring work (the house has the original
1948 wiring, and I'm going to be adding a lot of up-to-code circuits).
The house is a 1.5 story with a finished attic. When I took off one of
the floor heating vents in the attic (forced-air heat) and shone a
light down the opening, I discovered quite a bit of electrical wiring,
including a junction box, visible below. As far as I can tell, attached
to the box is a wall light fixture in a room on the main floor.

I haven't done a lot of further investigating yet (I didn't have a
powerful enough flashlight), but it looks like it might be the case
that the ducting is not continuous from the basement to the upper floor
- the whole section of wall between the two joists is being used as the
duct. This is obviously very bad - especially considering the
electrical wiring in the space. I'm planning to replace the wiring
anyways, so it won't be a problem, but I should do something about the
duct. What options, short of ripping up a section of wall on the main
floor, do I have? My fiancee is not going to be happy if I tell her
that we have to rip out a section of wall, though if that's the only
option, I guess I'll do it (at least that wall only has paneling, not
drywall).

It looks like the wiring is original, so that means that either someone
was careless at the time of construction, or some HVAC person did a
crappy job when adding a vent to the upstairs.

Any tips on how I should handle this? Thanks in advance.


My 1945 house had the same thing, but ONLY for the cold air returns. Still
an odd thing, though.

Before I'd start ripping walls down, call a local heating contractor and ask
about flexible ducting material. They use this stuff when updating really
old homes and they don't want to mess with the walls.


  #3   Report Post  
Posted to alt.home.repair
RayV
 
Posts: n/a
Default Whole wall as duct

Are you sure this is not a return vent? It is fairly standard to just
use the space between the studs to return air to basement. I have a
center wall in my two story house with several returns and the bulkhead
in the kitchen is open to the floor joists. System works fine.

  #4   Report Post  
Posted to alt.home.repair
Edwin Pawlowski
 
Posts: n/a
Default Whole wall as duct


wrote in message
It looks like the wiring is original, so that means that either someone
was careless at the time of construction, or some HVAC person did a
crappy job when adding a vent to the upstairs.


Are you sure it is a supply and not a return? In the 40's and 50's, it was
common to have an unlined air return and even fairly common to use it for
wiring. Returns have no heat to speak of, no pressures or things that will
cause problems.


  #5   Report Post  
Posted to alt.home.repair
PipeDown
 
Posts: n/a
Default Whole wall as duct

You could install a few fire dampers where the space transects the floor or
other places that make sense.

http://www.ul.com/regulators/dampers.cfm

Aside from the fire issue, leakage of the hot air out of the cavity might be
a concern for efficiency. Use of wall space for cold air return is common.
The under stair space in my prevoius 1973 home was used for cold air return
but a seperate return was used for the second floor.

There is nothing requiring you to change anything.

wrote in message
oups.com...
I've been doing a lot of poking around in my recently purchased house
in preparation for some major wiring work (the house has the original
1948 wiring, and I'm going to be adding a lot of up-to-code circuits).
The house is a 1.5 story with a finished attic. When I took off one of
the floor heating vents in the attic (forced-air heat) and shone a
light down the opening, I discovered quite a bit of electrical wiring,
including a junction box, visible below. As far as I can tell, attached
to the box is a wall light fixture in a room on the main floor.

I haven't done a lot of further investigating yet (I didn't have a
powerful enough flashlight), but it looks like it might be the case
that the ducting is not continuous from the basement to the upper floor
- the whole section of wall between the two joists is being used as the
duct. This is obviously very bad - especially considering the
electrical wiring in the space. I'm planning to replace the wiring
anyways, so it won't be a problem, but I should do something about the
duct. What options, short of ripping up a section of wall on the main
floor, do I have? My fiancee is not going to be happy if I tell her
that we have to rip out a section of wall, though if that's the only
option, I guess I'll do it (at least that wall only has paneling, not
drywall).

It looks like the wiring is original, so that means that either someone
was careless at the time of construction, or some HVAC person did a
crappy job when adding a vent to the upstairs.

Any tips on how I should handle this? Thanks in advance.





  #6   Report Post  
Posted to alt.home.repair
louie
 
Posts: n/a
Default Whole wall as duct

I agree with others in making sure this isn't just a return that you're
looking at. It's very much ok and normal to use a wall cavity for cold
air return, and not unusual to find electrical wiring running through
it. J-boxes are ok, but I think they have to be accessible and not
hidden in the wall, so that may be against code (you'll have to check
your local codes to be sure).

  #7   Report Post  
Posted to alt.home.repair
 
Posts: n/a
Default Whole wall as duct

Technically wiring shouldnt be in any ducts because the air flow will
spread fire fast, and be hard to put out. But its common to find in
cavitys, because it was easy and probably isnt a code issue on a
existing home

  #8   Report Post  
Posted to alt.home.repair
Pete C.
 
Posts: n/a
Default Whole wall as duct

" wrote:

Technically wiring shouldnt be in any ducts because the air flow will
spread fire fast, and be hard to put out. But its common to find in
cavitys, because it was easy and probably isnt a code issue on a
existing home


I believe BX, EMT and similar are ok to pass through plenums.

Pete C.
  #9   Report Post  
Posted to alt.home.repair
 
Posts: n/a
Default Whole wall as duct

I'm pretty sure it's not a cold air return (IIRC, there was hot air
coming out of it last time the heat was on). I agree that it's not a
problem if it's a cold air return, especially if I remove the wiring
that's there. I'll check next time I'm over at the house (I'm not
living there yet).

  #10   Report Post  
Posted to alt.home.repair
PipeDown
 
Posts: n/a
Default Whole wall as duct

I would guess; The attic was probably finished as a remodel and someone took
a shortcut routing the heating connection. Is there even a cold air return
for the attic or did they just assume it would flow down the stairs?

If it was an unpermitted remodel of the attic, make sure the joists are
built sufficient for a floor before you load that room with too much stuff
(might not make a good home gym)


wrote in message
oups.com...
I'm pretty sure it's not a cold air return (IIRC, there was hot air
coming out of it last time the heat was on). I agree that it's not a
problem if it's a cold air return, especially if I remove the wiring
that's there. I'll check next time I'm over at the house (I'm not
living there yet).





  #11   Report Post  
Posted to alt.home.repair
Goedjn
 
Posts: n/a
Default Whole wall as duct

On Wed, 19 Apr 2006 21:57:50 GMT, "Pete C."
wrote:

" wrote:

Technically wiring shouldnt be in any ducts because the air flow will
spread fire fast, and be hard to put out. But its common to find in
cavitys, because it was easy and probably isnt a code issue on a
existing home


I believe BX, EMT and similar are ok to pass through plenums.



Don't they make wire that's specifically rated
for use in plenums?

  #12   Report Post  
Posted to alt.home.repair
Pete C.
 
Posts: n/a
Default Whole wall as duct

Goedjn wrote:

On Wed, 19 Apr 2006 21:57:50 GMT, "Pete C."
wrote:

" wrote:

Technically wiring shouldnt be in any ducts because the air flow will
spread fire fast, and be hard to put out. But its common to find in
cavitys, because it was easy and probably isnt a code issue on a
existing home


I believe BX, EMT and similar are ok to pass through plenums.


Don't they make wire that's specifically rated
for use in plenums?


Yes, for comm. type wire like cat 5. It's not commonly found in power
type electrical wire though, the norm there is to use metal armored wire
like BX or metal conduit.

Pete C.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Duct Sizing Steve Groulx Home Repair 11 October 12th 05 11:11 PM
Cinder Block Retaining Wall Question [email protected] Home Repair 5 September 15th 05 06:12 PM
Wall falling down? Alex UK diy 8 August 29th 03 10:54 AM
Dry Rock Retaining Wall RedHeadAllDay Home Repair 4 August 18th 03 02:12 PM
Retaining Wall in front of another Retaining Wall MCL Home Repair 0 July 11th 03 03:48 PM


All times are GMT +1. The time now is 01:26 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"