eave vent rate
Am reroofing now & adding ridge vent, so need to know my eave air flow.
Have exposed 4x6 cedar rafters with 1x6 between them - no soffit. Each 1x6 has 3 (2" diam) holes backed with wire screen. In theory, I would think I have 3 x 6.28 sq in air flow reduced by the wire screen (50%?) per 1x6 board. The 'coons & squirrels have gotten through the screen multiple times over the years, so I've stapled a standard metal 4x16 undereave vent (air flow rated at 28 sq in each) to the backside of each 1x6. Now what do I have? |
#2
Posted to alt.home.repair
|
|||
|
|||
eave vent rate
Attic Ventilation rule...
Area of ceiling adjacent to the attic divided by 300 for a home less than 20 years old. (divide by 150 for older homes) Take resulting square ft and divide by 2 This will give you the required square feet of upper and matched reqired ventilation are for lower ventilation. Example: 2000 sq ft of ceiling / 300 = 6.7 6.7 / 2 = 3.3 The example home needs 3.3 square ft (480 sq inches) of upper ventilation and the same for lower ventilation. TAB Dude |
#3
Posted to alt.home.repair
|
|||
|
|||
eave vent rate
TAB Dude wrote:
Attic Ventilation rule... Area of ceiling adjacent to the attic divided by 300 for a home less than 20 years old. (divide by 150 for older homes) Explain this please. It's such a blanket (batt?) statement that I don't understand what you mean. R |
#4
Posted to alt.home.repair
|
|||
|
|||
eave vent rate
Attic Ventilation rule...
Area of ceiling adjacent to the attic divided by 300 for a home less than 20 years old. (divide by 150 for older homes) Thanks for looking, TAB Dude, but that's not the question. I think I know what my target *should* be. What I need to know is what rate I'm *now* getting for the eave part after combining the 2" holes & the metal eave vent. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Switch from variable rate to fixed rate mortgage? | Home Ownership | |||
Plumbing vent partially blocked by fascia | Home Repair | |||
OPTION ARM EXPLAINED: Pay what you want monthly mortgage. | Home Ownership | |||
OPTION ARM EXPLAINED: Pay what you want each month mortgage. | Home Ownership | |||
gable vent (bats!) - Attic ventilation | Home Repair |