In article , "Bill C" wrote:

Can someone please tell me what AWG copper line is required to service a
68.5 amp 240vac tankless water heater? The manufacturer recommends an 80
amp breaker.


Anywhere between #6 and #2. Depends on the temperature ratings of the
conductors, and how they're installed (cable, conduit, etc).

--