2000w is 16.7a. Since the circuit cannot carry more than 80% of maximum
capacity, you would need a 21a circuit. Since there is no such thing as a
21a circuit, you need the next larger size.
Even if you could get by with #12, why would you want to? #10 will give
much less voltage drop and the price isn't all that much different.