"Greg Deputy" wrote in message
...
Yeah, the transformer diagram indicates 110v out the secondary, and has 2
configurations for the primary, 440v or 220v.


For low voltage operation you place the primary windings in series with one
another.


So how would one normally go about rewiring the motor for 220v? Is it
likely i'm going to need direct access to the motor? As installed it is

all
buried inside the cabinet, so i guess i'll have to pull the thing out.


Yup, you also gotta rewire the taps inside the motor's peckerhead for low
voltage operation--the connection diagrams should be on the motor's
data-plate.

--