Garage Power Shopping List
On Sun, 15 Feb 2004 13:26:35 +0000 (UTC), " Tim \(Remove NOSPAM."
wrote:
"manoman" wrote in message
...
I would really appreciate it if you guys could look at this a see if I
have
I missed anything obvious?
Cable:
3core x 4mm Armoured Black 25m Coil
Why not use 2 core?
You'll use the armour as the earth- isolated at the shed end (plastic
comsumer unit) and connected at the house end (metal knock out box connected
to earth- NB 10mm2 cable here please)
You'll need some more 10mm2 earth cable and a copper earth spike at shed.
[1]
Assuming TT system.
I think we're getting a little over complex here, see many previous
posts about earthing arrangements to outbuildings.
...
SJW
A.C.S. Ltd.
|