Default RCD to protect hedge trimmer

F news@nowhere Wrote in message:
I bought a 2 gang RCD socket from Screwfix (code 3133J) to replace a 2
gang socket in the garage which I use to power the hedge trimmer. Once I
got it home the installation guide says that as it's latched it's 'not
suitable for outdoor power tools and garden equipment'.

Is it an absolute no-no? If it is, can anyone suggest an alternative?

--
Frank

Not an absolute no no after all most RCDs fitted to CUs are
passive they trip and stay tripped in the case of earthleakage
but if there is a "normal" power interruption they don't need
your intervention when the power is restored (think of your
fridge & freezer).
An active (non latching) RCD is a better choice for power tools
etc. because the tool won't start up unexpectedly when the power
is restored.
--