Lighting circuit - radial tree allowed?
View Single Post
#
4
Posted to uk.d-i-y
ARW
external usenet poster
Posts: 10,161
Lighting circuit - radial tree allowed?
On 20/05/2020 09:56,
wrote:
On Wednesday, 20 May 2020 09:29:29 UTC+1, JimK wrote:
I have a bathroom fan to fit in the loft for which I'll break into
& spur off the radial lighting circuit.
Whilst doing that I thought I should install a simple loft light.
Can I do both these things on the same spur off the lighting
radial circuit? In effect making a branch with two fixtures on
it?
Yes.
There isn't really a concept of a "spur" as it's a radial circuit and there are no limits to the number or direction of branches.
Fit a local isolator to the fan as otherwise you'll have to turn off the loft light to work on the fan in the dark
Plus it's an electrical reg to fit an isolator for a fan:-)
--
Adam