"HeatMan" wrote in message link.net...
"Harry K" wrote in message
om...
"HeatMan" wrote in message

k.net...
Yeah, but run a leaking one to a drain?


The TPR valve should -always- be run to a drain, code or no code.
Just picture what happens if the valve opens and fails to close again
(yes it happens). You now have an open connection to the service line
that will continue to spew water until someone shuts it off. No
drain?? Where do you think the water is going to go??

Harry K


First off, local codes (read LOCAL) do not require the relief valve to be
run to a drain. The code requires the pipe to be run to a point a few
inches above the ground. Running the pipe to a drain is a plus.


I'm curious. Just how do you know that no local codes don't do that?

Second, and more important(!), the question was who told the OP to run a
leaking pipe to a floor drain. If the relief is leaking, there is a problem
and running it to a floor drain will simply hide the problem. You need to
learn how to read.


What got your panties in a bunch? I posted a comment to others
pointing out that just pointing a TPR overflow to the floor (or
elsewhere) is not a good practice. If you think I mean to connect it
to the drain, I don't. You must ahve an air gap and a blowing pipe
into a drain will be notice enough. You seem to think that suddenly
discovering water everywhere on the floor is a 'good thing'. As to
reading, I do just fine, you don't do so well in the logic department
tho.


Oh, and yes, the relief valves do pop and run continuously. If it's in an
older house with a 1.25 inch or a 1.5 inch floor drain (and it does happen,
I'm sitting about 14 feet from a 1.5 inch floor drain), don't you think
65-120 psi will overpower the draining capacity of such a small drain?


Again your seem to think that a flooded floor is a 'good thing'. Yes
it can overwhelm the drain so just let it blow eh??

While I'm at it, have you ever seen the pipe off a relief valve drain
upwards? I see them almost daily...... New codes require there to be some
way to drain the water off the seat of the valve.


So all -local- codes require that now??. Just how does pointing the
pipe -up- drain the valve seat and just where is all that water
spraying to??

Harry K