2nd kitchen circuit??
On Monday, 30 September 2019 17:56:26 UTC+1, wrote:
Hi All,
Current load on kitchen ring 32A MCB) is
Wishdosher, washing machine, tumble drier, fridge freezer, kettle, toaster, microwave, I think thats most of the regular appliances.
I was wondering about moving say the wishdosher and washing machine onto a radial. I could easily reroute an unused 2.5mm T&E into the kitchen and connect the other end to a new 16 or 20 A MCB (or have a part P person do so).
What does the team think?
Are you getting mcb trips? If not... 32A rings routinely supply much more than 32A.
NT
|