On 30/09/2019 17:56, wrote:
Hi All,

Current load on kitchen ring 32A MCB) is

Wishdosher, washing machine, tumble drier, fridge freezer, kettle, toaster, microwave, I think thats most of the regular appliances.

I was wondering about moving say the wishdosher and washing machine onto a radial. I could easily reroute an unused 2.5mm T&E into the kitchen and connect the other end to a new 16 or 20 A MCB (or have a part P person do so).

What does the team think?

OK I don't have the tumble dryer, but I have the rest (and more) and
have never blown the MCB.