View Single Post
  #32   Report Post  
Posted to alt.home.repair
Stormin Mormon[_10_] Stormin Mormon[_10_] is offline
external usenet poster
 
Posts: 10,730
Default Square D electrical panel question

On 3/4/2016 9:39 PM, wrote:
On Fri, 4 Mar 2016 16:56:37 -0800 (PST), Uncle Monster
Shouldn't the ground be connected to the
separate ground bar?

Should I move the ground wire?


Perhaps I phrased it incorrectly. Does the sub panel can/housing have to grounded? I may have the wrong vision in my head but I think I imagined that the ground bar was in an insulated holder like the neutral bar but now I remember the grounding bar being attached directly to the can/housing. Drain bamage, not enough sleep. Sometimes I can't spell kat. o_O

[8~{} Uncle Confused Monster

The can/housing of ALL panels needs to be grounded, as does every
switch and outlet box, as well as all utility boxes. ONLY in the
"main/service disconnect" may the neutral and ground be directly
connected. The neutral bonding screw or jumper connects the neutral
buss to the case ground.


Anyone wish to answer the OP's OQ?

--
..
Christopher A. Young
learn more about Jesus
..
www.lds.org
..
..