On 12/26/2015 10:31 AM, wrote:
On Sat, 26 Dec 2015 03:59:28 -0600,
wrote:

If it's still unbalanced with everything OFF, it's just a transformer
that's a little unbalanced. Not to be worried about, if that's all it
is.



Huh?
They don't arbitrarily "center tap" the transformer wherever they
want,. It is wound at the factory and it will be tapped exactly at the
center.
This looks more like a 5-6% voltage drop in the neutral.
That is far beyond the NEC recommendation and the utility standard.


Sounds like it's not to code, and will affect
the OP's insurance?

--
..