Default Extending ring mains

In article ,
Adam Funk wrote:
On 2015-12-08, Dave Plowman (News) wrote:


In article ,
Adam Funk wrote:


It makes no difference if you extend the ring or use a spur. You
should ensure sure that the current carrying capacity of the cable
does not drop below 20A.


There's nothing to stop a future occupier from plugging two kettles
in, though (I'm assuming it's a double socket). ;-)


Modern kettles are generally 10 amps maximum.


Really? Ours isn't more than a couple of years old & it's the full
13 A.



The vast majority use the standard kettle connector. Rated at 10 amps.

--