Doug Miller wrote:
On 9/3/2011 5:40 PM, -MIKE- wrote:
On 9/3/11 3:40 PM, Bill wrote:
Am try to install new garbage disposal and have a quick electrical
quesiton.

GD Unit came with (3-prong) electrical cord attached. Unfortunately the
cord does not seem to be removable. Can I cut off the plug and attach
this to the romex in my junction box?


Short answer: yes. As long as the romex wire is copper and not aluminum.


Sorry, that's *not* correct: flexible cord is not Code-approved for
permanent connection to the wiring system except under limited
circumstances that do not pertain here.


I'm surprised it is allowed to use a flexible cord which, because of the
nature of the device, has such a high probability of laying in water at
some point if the 36" cord is merely plugged in. I won't let the cord
rest on the bottom surface.

Admittedly, the cord appears to be of very good quality. Surely it is
waterproof unless it cracks.