On 6/20/10 8:04 AM, Doug Miller wrote:
In ,
lid wrote:
If the NEC won't let you put Romex into a conduit
A common misconception.
There is *nothing* in the NEC which prohibits putting NM ("Romex") in conduit;
quite the contrary, in fact: Article 334.15(B) _explicitly requires_ putting
it in conduit for "protect[ion] from physical damage where necessary".
I did that on the new 220 circuit to my table saw. I was going to use
those separate, loose wires, but the Romex was actually cheaper, and I
needed it for another run.
--
-MIKE-
"Playing is not something I do at night, it's my function in life"
--Elvin Jones (1927-2004)
--