In article ,
lid wrote:
If the NEC won't let you put Romex into a conduit
A common misconception.
There is *nothing* in the NEC which prohibits putting NM ("Romex") in conduit;
quite the contrary, in fact: Article 334.15(B) _explicitly requires_ putting
it in conduit for "protect[ion] from physical damage where necessary".