Installing a subpanel
"Steve Barker" wrote in message
...
"RBM" wrote in message
...
Probably. If the panel you're calling a sub panel, is fed from the
other
panel, it is in fact a sub panel, and must have separate busses. You can
however have up to six panels with main disconnects in each of them, and
each would be treated as a main panel, and grounds and neutrals would be
bonded together in all of them
and each of these six panels would be fed how? to qualify for this
scenario?
thanks
steve
They could each be nippled out of a gutter trough where they would be
bugged onto the service main feeders, as one possible example
|