Default Ring Main Extension - Done Incorrectly ?

In article
,
wrote:
We have just moved into a new 1960s house and the upstairs ring main
has been extended into the loft by drilling a hole through the wall of
the back of a socket in one of the bedrooms into the airing cupboard.


2 X 2.5mm T+E then loops round the loft and back to the socket. So..
in the back of my socket I have 4 pairs of wires attached.


This to me seems wrong. I would have added a junction box in the
airing cupboard and then run one of the existing wires to that. I
would then loop from there round the loft and back to the socket.


Can anyone confirm if the way it's been done is acceptable. I would
have thought that this setup would mean an imbalance in the current
travelling round the ring.


Remove the socket. Couple one end of the original ring to the extension
upstairs using a suitable choc block. The other two cables to the socket.
You now have a normal ring.

--