Ray wrote:

Why can you not use the "RCD Consumer Unit" as an isolator?


Because the CU also supplies lights & patio power sockets


OK, fair enough...

Is it actually isolation you need or functional switching?


Isolation for the hot tub only


A 3kW hot tub will actually only draw 13A not 25A. Hence a simple double
pole switch such as:

http://www.tlc-direct.co.uk/Main_Ind..._20/index.html

would be fine.

If you really feel you need the ability to switch 25A for some reason then:

http://www.tlc-direct.co.uk/Main_Ind..._45/index.html

Would do the trick.



--