John Ross wrote:


These are 2 prong outlets. Those testers are for 3. Is there a way to
test the 2 prong outlets?
John


You can use a neon tester
http://www.acehardware.com/product/i...entPage=family
The neon 'lamp' has 2 parallel rods and it glows orange on voltage (like
a neon sign). Plug one lead into a receptacle slot and touch the other
lead. The lamp will glow *very dimly* if the slot is 'hot'. You probably
will have to cup you hand around it to block other light. These lamps
work at very low current and can light even if you are insulated from
everything (capacitive current).

There are also many 'non-contact' voltage detectors like
http://www.toolbarn.com/product/gree...9022/?ref=base
that light up or make sound when placed at the 'hot' receptacle slot.
(Some may have to be closer to the conductor - don't know about this one.)

--
bud--