Pete C. wrote:
Ed wrote:
I have a siemens panel, and I got some #4 stranded copper wire to
connect to the ground rods, and water pipes. But when I go to connect
it to the ground/neutral bar, it is too big(just a little too big) to
fit in the slots. Is there another peice that is supposed to be for
this, or do I need to go back and get solid #4 for the ground wire (and
will solid #4 fit).

Thanks!


You can divide the strands into two bundles (like a Y) and connect in
two adjacent slots if you need to.

Pete C.


No competent electrical inspector will ever except that. Buy the
correct lug and install it.
--
Tom Horne