Default ground wire on siemens panel

On 9 Aug 2006 11:07:44 -0700, "Ed" wrote:

I have a siemens panel, and I got some #4 stranded copper wire to
connect to the ground rods, and water pipes. But when I go to connect
it to the ground/neutral bar, it is too big(just a little too big) to
fit in the slots. Is there another peice that is supposed to be for
this, or do I need to go back and get solid #4 for the ground wire (and
will solid #4 fit).

Thanks!


imho:

Go to a electrial supply shop and get an add-on neutral lug for your
panel, remember to follow all electrial codes.

Example of what one looks like: http://www.urlbee.com?7778

or google "neutral lug"

hth,

tom