Woodworking (rec.woodworking) Discussion forum covering all aspects of working with wood. All levels of expertise are encouraged to particiapte.

Reply
 
LinkBack Thread Tools Search this Thread Display Modes
  #1   Report Post  
Steve DeMars
 
Posts: n/a
Default What size A/C unit for shop?

I am in the process of building a general purpose / woodworking shop.

Location - Baton Rouge, LA - high humidity area

Two small 3' wide X 2' high insulated windows facing south very near the
top of the walls.

Size will be 20' X 22' (440 sq. ft.) with 10' ceilings.

Walls will be 4" - drywall / R-15 batt / 7/16" OSB / Hardie Plank.

Ceiling will be - drywall / R-49 batt / to open attic.

Attic will be well ventilated with (2) 14" turbines.

Roof will be shingled with Solar Board for roof decking.

Any suggestions appreciated . . . . . would really like to hear from someone
living in this climate with a simular sized insulated shop . . . .
Steve


  #2   Report Post  
Edwin Pawlowski
 
Posts: n/a
Default


"Steve DeMars" wrote in message
news:dGPOe.1436$tB5.862@okepread06...
I am in the process of building a general purpose / woodworking shop.

Location - Baton Rouge, LA - high humidity area

Two small 3' wide X 2' high insulated windows facing south very near the
top of the walls.

Size will be 20' X 22' (440 sq. ft.) with 10' ceilings.


HVAC pros use a Manual J for calculations. There are some web sites that do
have some basic programs that will be close.
http://whirlpoolcoolingcalc.e-net.co...or/default.asp

I don't know what assumptions they make for insulation, window type,
construction type, etc. There may be more accurate ones than this.
--
Ed
http://pages.cthome.net/edhome/


  #3   Report Post  
Howard
 
Posts: n/a
Default

Ask whoever is sizing the AC to consider that you will be running tools
such as a dust collector and airfilter plus significant lighting while
trying to cool the shop. The motor and lighting load is significant.
All of it will become heat within your shop.

  #4   Report Post  
gw
 
Posts: n/a
Default


wrote in message
...
On Tue, 23 Aug 2005 20:03:02 -0500, "Steve DeMars"
wrote:

I am in the process of building a general purpose / woodworking shop.

Location - Baton Rouge, LA - high humidity area

Two small 3' wide X 2' high insulated windows facing south very near

the
top of the walls.

Size will be 20' X 22' (440 sq. ft.) with 10' ceilings.

Walls will be 4" - drywall / R-15 batt / 7/16" OSB / Hardie Plank.

Ceiling will be - drywall / R-49 batt / to open attic.

Attic will be well ventilated with (2) 14" turbines.

Roof will be shingled with Solar Board for roof decking.

Any suggestions appreciated . . . . . would really like to hear from

someone
living in this climate with a simular sized insulated shop . . . .
Steve


My guess, 9,000BTU +/- 1000
A big window shaker.

That would work in Florida


Just for comparison, I live in Maine, and in a 32 x 24 with 8ft ceilings, a
10,000 BTU window unit BARELY cuts it on 85+ degree days with tools running.
Should have gotten the 12,000.


  #5   Report Post  
User Example
 
Posts: n/a
Default

Just for comparison, I live in Maine, and in a 32 x 24 with 8ft ceilings, a
10,000 BTU window unit BARELY cuts it on 85+ degree days with tools running.
Should have gotten the 12,000.


I live in Austin, TX. I had a 12000 BTU portable A/C in my garage and
it didn't do squat. I have a 24000 BTU mini split on order.


  #6   Report Post  
RonB
 
Posts: n/a
Default

Sounds like you are taking care of insulation concerns. I personally think
sizing it for equivalent residential floorspace would put you in the
ballpark. The machines in my shop certainly won't generate any more heat
than our range, hair dryers, microwaves, televisions, etc. Also, unless you
have a lot of helpers hanging around the body-temp effect should be less.

BTW, I live in south central kansas. Admittedly a little less humid that
your neighborhood. However 100 degrees and mid 70s humidity is common.
Today is expected to hit 90/90 (degrees/humidity). Come on October.

Buy lots of filters.

RonB


  #7   Report Post  
User Example
 
Posts: n/a
Default

I live in Austin, TX. I had a 12000 BTU portable A/C in my garage and
it didn't do squat. I have a 24000 BTU mini split on order.



You don't figure that garage door was losing a lot of your cooling do
you? What was the R factor of your walls?

The OP is talking about a pretty tight room.
In Louisiana humidirty is an issue and oversizing a unit will just
make it worse.


I had cellulose blown into all walls. The door is insulated and has
weathstripping on all sides. The ceiling has 6"-12" of insulation
depending on location.

I imagine that the garage door was still leaking some but I had it about
as insulated as I could get it.
  #8   Report Post  
User Example
 
Posts: n/a
Default

I had cellulose blown into all walls. The door is insulated and has
weathstripping on all sides. The ceiling has 6"-12" of insulation
depending on location.

I imagine that the garage door was still leaking some but I had it about
as insulated as I could get it.



You have something creating a big heat load. The rule of thumb for old
Florida CBS houses, virtually no insulation and leaky awning windows
is a ton per 400- 500 sq ft..


I do have a gas water heater in the garage. It is in a closet but the
door and closet are leaky. I have wondered if causes it to stay warm.

The funny thing is that in the winter I can easily heat the garage to a
nice level using a $15 heater the size of a shoe box. But I can't cool
it for anything. That's why I went overkill on the 2ton A/C.
  #9   Report Post  
Norman D. Crow
 
Posts: n/a
Default


wrote in message
...
On Wed, 24 Aug 2005 13:17:55 GMT, User Example
wrote:

I live in Austin, TX. I had a 12000 BTU portable A/C in my garage and
it didn't do squat. I have a 24000 BTU mini split on order.



You don't figure that garage door was losing a lot of your cooling do
you? What was the R factor of your walls?

The OP is talking about a pretty tight room.
In Louisiana humidirty is an issue and oversizing a unit will just
make it worse.


Yep! Ever been in an adult beverage establishment that was nice & cool but
felt "clammy"? Too big an A/C unit, chills & stops cooling without taking
the humidity out of the air. I'd a lot rather have a slightly undersize unit
that may not get quite as cold as you want, but runs constantly, sucking the
humidity out of the air. The low humidity will make it feel cooler than it
is.

--
Nahmie
The greatest headaches are those we cause ourselves.


  #10   Report Post  
Joe Nation
 
Posts: n/a
Default


The number of lights and other electric motors that will be continuously or
intermittently running will have a drastic effect on your heat load. If you
are running an air cleaner and a dust collector continuously the electric
motors that power them will give off considerable heat that the air
conditioner will have to remove to bring the temperature down. For example,
when I run a 3 hp Unisaw, a 3 hp dust collector, a 1/3 hp air cleaner and 6
eight foot forusent light strips at the same time, that will overwhelm a
18,000 BTU air conditioner. My shop is located in West Texas near Abilene.
My shop is in a metal building with 3 inches of insulation on the walls and
ceiling. It is 24' X 24' and the air conditioner will maintain a 72 degree
temperature with these appliances turned off and heat up rapidly if
everything is turned on at the same time when the outside temperature is
above 80 -85 degrees.

Also, the 12" planer, and the 1½ hp drum sander when used for extensive
periods of time will heat up the shop.


Howard" wrote in message
ups.com...
Ask whoever is sizing the AC to consider that you will be running tools
such as a dust collector and airfilter plus significant lighting while
trying to cool the shop. The motor and lighting load is significant.
All of it will become heat within your shop.





  #11   Report Post  
Brandon
 
Posts: n/a
Default

Steve

I just built a 26'X36'workshop in Lake Charles, LA. Ceilings are 8 ft
around perimeter with 18'X 20' tray 9'6" high in the center. I went
with a 2 1/2 ton heat pump on the advice of my a/c guy. He had
originally suggested/priced a 2 ton unit, but changed his mind after
seeing the shop. I got electricity turned on at about 4:30 yesterday
evening, but had to leave for work this morning. Unfortunately, I'll
be gone for 21 days, any performance data I could give you would
probably be too late.

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Fedders Window AC Unit Dead--Diagnostic Advice? Lovegas Home Repair 11 August 8th 05 03:48 AM
Size of Geothermal Unit [email protected] Home Repair 17 June 7th 05 04:14 PM
Google Desktop Problems indexing Netscape mails hampi Metalworking 0 June 7th 05 02:08 PM
Copper pipe sizing. Is bigger better? Paul J Home Repair 19 February 29th 04 07:52 PM
wires to capacitor on YORK AC unit are burned and melted Keith Reding Home Repair 58 February 18th 04 03:38 PM


All times are GMT +1. The time now is 09:07 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"