#1
![]() |
|||
|
|||
![]()
Hi
Im going to change a boiler - the current system is an ideal E type non pressurised system, hot water tank and with microbore feed to radiators. - I would like to install a large combi with a store facility (I suppose I like the idea of instant water and heating only the water I require) - doing away with a leaking hot water tank and header tanks. Questions 1) Can I use a combi with micro bore? 2) If I can not, is there anything special I need? ie a dam big pump? 3) What happened to the copper hot water tank, is this megaflow thingy the replacement - have you seen the price of those things!!!!! Thanks for all info Cameron |
#2
![]() |
|||
|
|||
![]()
On Mon, 17 Jan 2005 00:30:07 +0000, Cameron wrote:
Hi Im going to change a boiler - the current system is an ideal E type non pressurised system, hot water tank and with microbore feed to radiators. - I would like to install a large combi with a store facility (I suppose I like the idea of instant water and heating only the water I require) - doing away with a leaking hot water tank and header tanks. Questions 1) Can I use a combi with micro bore? 2) If I can not, is there anything special I need? ie a dam big pump? 3) What happened to the copper hot water tank, is this megaflow thingy the replacement - have you seen the price of those things!!!!! Thanks for all info Cameron 1) yes 2) see 1 3) They're alive and well and covered with 50mm of blue PU foam. Used when and where it's appropriate. I recommend you read the FAQs and decide for yourself whether a combi is right for you, which you may have done already. To combi or not to combi is a question not an article of faith. -- Ed Sirett - Property maintainer and registered gas fitter. The FAQ for uk.diy is at www.diyfaq.org.uk Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html |
#3
![]() |
|||
|
|||
![]()
Many thanks
Cameron |
#4
![]() |
|||
|
|||
![]() Quote:
Hot water cylinders 117 litres £88 trade at City Plumbing. Why not get a new one? |
#5
![]() |
|||
|
|||
![]() "Cameron" wrote in message ... Hi Im going to change a boiler - the current system is an ideal E type non pressurised system, hot water tank and with microbore feed to radiators. - I would like to install a large combi with a store facility (I suppose I like the idea of instant water and heating only the water I require) - doing away with a leaking hot water tank and header tanks. Good idea. Questions 1) Can I use a combi with micro bore? Yes. 2) If I can not, is there anything special I need? ie a dam big pump? 3) What happened to the copper hot water tank, is this megaflow thingy the replacement - have you seen the price of those things!!!!! Get a highflow combi, Alpha CD 50 Worceter Bosch Greenstar 40Kw, etc. _________________________________________ Usenet Zone Free Binaries Usenet Server More than 120,000 groups Unlimited download http://www.usenetzone.com to open account |
#6
![]() |
|||
|
|||
![]() "Paul Barker" wrote in message ... Cameron Wrote: Many thanks Cameron R the Ideal 'E' Type. What a wonderful boiler. You'll never again know such a well crafted beast built for longevity. Welcome to the disposable boiler society, fairwel to a Rolls Royce. If youn want RR quality today you can get it. Eco-Homtec (MAN), Viessmman, Quantum (in Burnley). If you want boioers with a 15 years life span then go to B&Q, and pay buttons. The B&QW boioers are fine. They do their job well when you consider the price. Also what made boilers reliable was the controls, which no boiler manufacturer makes. I recall the McLaren multi-function control valve, that was troublesome compared to the Honeywell. In many cases the boilers they were fitted on were v good, but people slid away from them because of the controls. In many cases the makers switched to Honeywell, but dumb plumbers would still not buy the boilers because of the McLaren problems, which no longer existed. Hot water cylinders 117 litres £88 trade at City Plumbing. Why not get a new one? Get two at that price. Or better still get a W-B combi, 40kW _________________________________________ Usenet Zone Free Binaries Usenet Server More than 120,000 groups Unlimited download http://www.usenetzone.com to open account |