Default Adding extra radiators. Help!

We have a small one bedroomed house heated by a combi-boiler and, at the moment, four radiators. Basically I want to add a couple of extra radiators in the small hallways (if thats the right term, they ARE small) at the front and rear of the house.
My plumbing experience so far consists of moving and replacing two radiators and I'm reasonably confident with pipework. I have tried reading up as much as possible and know a little about flow and return pipes and not connecting radiators in series. What I'm not sure about is how I connect up the two extra radiators as there is no access (without major work) to the flow and return pipes coming from/to the boiler. I do have access (from the cellar) to the 15mm pipes feeding the living room radiator though. Can I tap into these? As far as I can tell, the flow/return pipes from the boiler simply run vertically down the wall (boxed in and behind work surface)from the boiler in the bathroom and come to an end below floor level in the corner of the kitchen directly below with 15mm pipes coming off feeding each of the four radiators.
Hope I've made myself clear and not waffled too much - first post!
Any advice greatly appreciated.
  #2   Report Post  
John Rumm
 
Posts: n/a
Default

Raif wrote:

the living room radiator though. Can I tap into these? As far as I can


The short answer is yes.

As long as the living room radiator is not huge (and hence using all the
capacity of the 15mm pipework) you should be fine. Even then it sounds
like you only need to add small extra rads so its unlikely to be a
problem either way.

--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
  #3   Report Post  
Junior Member
 
Posts: 2
Default

Quote:
Originally Posted by John Rumm
Raif wrote:

the living room radiator though. Can I tap into these? As far as I can


The short answer is yes.

As long as the living room radiator is not huge (and hence using all the
capacity of the 15mm pipework) you should be fine. Even then it sounds
like you only need to add small extra rads so its unlikely to be a
problem either way.

--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
Thanks.
Thought/hoped that might be the case. Not sure if the two current radiators on each floor are connected independently to the flow and return pipes from the boiler or whether one feed covers two radiators - if you see what I mean?!
When you say huge, how huge is huge? ie what is the capacity of the 15mm pipework?
  #4   Report Post  
Christian McArdle
 
Posts: n/a
Default

I do have access (from the cellar) to the 15mm pipes feeding
the living room radiator though. Can I tap into these?


It is quite likely that you can just use those pipes. 15mm pipework is good
for 6kW, IIRC, which easily runs 1 large and 2 small radiators. My 3 bed
house was plumbed with each floor sharing one 15mm run, joined together by
22mm runs to the boiler, although I've modified it so that each 15mm run is
off its own zone valve, with a new 22mm to the loft where the boiler is.

Your main problem is if the main trunk of your system is run in 15mm, which
could be quite marginal to run a 1 bedroom house from. You may need to turn
the pump up in this case and it might get noisy in some circumstances. If
so, consider replacing the pump with a Grundfos Alpha model. This would be
cheaper than replacing the congested sections with 22mm, although, perhaps
not quite as effective.

Christian.


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
combi fed radiators gurgle Fred UK diy 5 December 1st 04 05:41 PM
Radiators - standard sizes? Charles Middleton UK diy 4 November 3rd 04 05:22 PM
Why do Radiators warm up when the hot water is on? Miles UK diy 7 October 16th 04 05:27 PM
Question regarding adding an extra socket to the ring main Fiona Reid UK diy 10 September 3rd 03 04:45 PM


All times are GMT +1. The time now is 04:37 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"