Hi,

We have a Baxi Barcelona which according to the blurb has two ways to
connect the pump, one for fully TRV'd systems and the other when used with a
bypass. The fully TRV'd one runs the pump from a separate connection from
the boiler so that the pump shuts off when the boiler does - the other way
being to run it as normal via the timer feed to the boiler.

But running it in this way makes the pump stop when the boiler is not
firing, even when the mains to the boiler is on. Is that normal? I thought
pumps usually ran all the time.

Thanks.


  #2   Report Post  
Ed Sirett
 
Posts: n/a
Default

On Tue, 12 Oct 2004 19:48:14 +0000, Someone wrote:

Hi,

We have a Baxi Barcelona which according to the blurb has two ways to
connect the pump, one for fully TRV'd systems and the other when used with a
bypass. The fully TRV'd one runs the pump from a separate connection from
the boiler so that the pump shuts off when the boiler does - the other way
being to run it as normal via the timer feed to the boiler.

But running it in this way makes the pump stop when the boiler is not
firing, even when the mains to the boiler is on. Is that normal? I thought
pumps usually ran all the time.


Someone (who ought to have known better in IMHO) decided in the design
that unlike all other modern boilers which have a permanent live and
switched (demand) live connections the BB
would work like an older style boiler with a simple apply-mains-and-it'll-
start design.

The boiler tries to work out when there is little flow and cut the pump
and gas for a while but of course it can't do any pump over-run to remove
excess heat if it stops in full flight.

You can make of this what you will, of course.

--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html


  #3   Report Post  
Someone
 
Posts: n/a
Default

Someone (who ought to have known better in IMHO) decided in the design
that unlike all other modern boilers which have a permanent live and
switched (demand) live connections the BB
would work like an older style boiler with a simple apply-mains-and-it'll-
start design.

The boiler tries to work out when there is little flow and cut the pump
and gas for a while but of course it can't do any pump over-run to remove
excess heat if it stops in full flight.


I blindly followed the manual but thinking about it, and what you point out,
would it seem better to run the pump all the time anyway? Otherwise when the
boiler stops al the water just sits in each rad cooling at its own rate and
nothing will then happen until the boilers own water cools and it decides to
burn again. We have an always-on rad anyway that is capable of being the
by-pass.

I'm gonna check with Baxi techs anyway but an I daft in my thinking (which
would not surprise me!) ?



  #4   Report Post  
Ed Sirett
 
Posts: n/a
Default

On Wed, 13 Oct 2004 11:42:37 +0100, Someone wrote:

Someone (who ought to have known better in IMHO) decided in the design
that unlike all other modern boilers which have a permanent live and
switched (demand) live connections the BB
would work like an older style boiler with a simple apply-mains-and-it'll-
start design.

The boiler tries to work out when there is little flow and cut the pump
and gas for a while but of course it can't do any pump over-run to remove
excess heat if it stops in full flight.


I blindly followed the manual but thinking about it, and what you point out,
would it seem better to run the pump all the time anyway? Otherwise when the
boiler stops al the water just sits in each rad cooling at its own rate and
nothing will then happen until the boilers own water cools and it decides to
burn again. We have an always-on rad anyway that is capable of being the
by-pass.

I'm gonna check with Baxi techs anyway but an I daft in my thinking (which
would not surprise me!)


You are not daft who ever designed Barcelonas should have stayed home that
day.

--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Heat banks (again!) Dave UK diy 148 September 6th 04 08:45 PM
Pump question (not a shower pump!) T i m UK diy 4 April 10th 04 08:56 AM
Another heating problem question! David Hearn UK diy 9 December 12th 03 08:29 PM
Sump pump question. Pradeep Krishna Home Repair 3 September 2nd 03 07:34 PM
Further to my last post entitled 'Flushing and treating central heating question' David W.E. Roberts UK diy 0 July 29th 03 07:15 PM


All times are GMT +1. The time now is 05:40 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"