Connecting sinks etc to smelly septic system
Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where.
We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? george |
#2
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
"George Miles" wrote in message
... Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? Does that requirement apply to existing installations or only to new ones? And does it apply to *all* grey water - baths, washbasins, washing machines - ie all water except rainwater from gutters? I ask because my parents have a holiday cottage where only the toilets drain into the septic tank, and everything else goes into a communal grey water drain for the village which goes, like yours, "we know not where". I think it ultimately drains into local beck. I had always understood that baths, in particular, were not to go into a septic tank because of the large amount of water which could overwhelm the drainage rate of the septic tank's outflow (into the same communal drain, I imagine!), and were actively encouraged to go into soakaway etc. |
#3
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
On Sunday, February 17, 2019 at 4:27:14 PM UTC, NY wrote:
"George Miles" wrote in message ... Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? Does that requirement apply to existing installations or only to new ones? And does it apply to *all* grey water - baths, washbasins, washing machines - ie all water except rainwater from gutters? I ask because my parents have a holiday cottage where only the toilets drain into the septic tank, and everything else goes into a communal grey water drain for the village which goes, like yours, "we know not where". I think it ultimately drains into local beck. I had always understood that baths, in particular, were not to go into a septic tank because of the large amount of water which could overwhelm the drainage rate of the septic tank's outflow (into the same communal drain, I imagine!), and were actively encouraged to go into soakaway etc. interesting questions, i dont know the answer yet! george |
#4
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
On 17/02/2019 20:26, Chris Hogg wrote:
On Sun, 17 Feb 2019 16:27:11 -0000, "NY" wrote: "George Miles" wrote in message ... Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? Does that requirement apply to existing installations or only to new ones? And does it apply to *all* grey water - baths, washbasins, washing machines - ie all water except rainwater from gutters? I ask because my parents have a holiday cottage where only the toilets drain into the septic tank, and everything else goes into a communal grey water drain for the village which goes, like yours, "we know not where". I think it ultimately drains into local beck. I had always understood that baths, in particular, were not to go into a septic tank because of the large amount of water which could overwhelm the drainage rate of the septic tank's outflow (into the same communal drain, I imagine!), and were actively encouraged to go into soakaway etc. In my previous property, everything went into the septic tank except rainwater. In my current property, the same, but it is a proper sewage treatment system. -- "The great thing about Glasgow is that if there's a nuclear attack it'll look exactly the same afterwards." Billy Connolly |
#5
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
On Sun, 17 Feb 2019 20:26:05 +0000, Chris Hogg wrote:
On Sun, 17 Feb 2019 16:27:11 -0000, "NY" wrote: "George Miles" wrote in message ... Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? Does that requirement apply to existing installations or only to new ones? And does it apply to *all* grey water - baths, washbasins, washing machines - ie all water except rainwater from gutters? I ask because my parents have a holiday cottage where only the toilets drain into the septic tank, and everything else goes into a communal grey water drain for the village which goes, like yours, "we know not where". I think it ultimately drains into local beck. I had always understood that baths, in particular, were not to go into a septic tank because of the large amount of water which could overwhelm the drainage rate of the septic tank's outflow (into the same communal drain, I imagine!), and were actively encouraged to go into soakaway etc. In my previous property, everything went into the septic tank except rainwater. Ditto. Small rural village with a block of cottages having a communal septic. They are up in arms at the prospect of having to fork out a lot of money to meet whatever is being proposed. I've been out of it for a couple of years so hopefully no come-back in my direction. -- AnthonyL |
#6
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
AnthonyL posted
On Sun, 17 Feb 2019 20:26:05 +0000, Chris Hogg wrote: In my previous property, everything went into the septic tank except rainwater. Ditto. Small rural village with a block of cottages having a communal septic. They are up in arms at the prospect of having to fork out a lot of money to meet whatever is being proposed. I've been out of it for a couple of years so hopefully no come-back in my direction. It isn't being proposed. It's happening. Regulations imposed courtesy of an EU near you. -- Evremonde |
#7
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
On 17/02/2019 16:19, George Miles wrote:
Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? george Best will be U bends at each source but if that is not practical as many as possible. You will also need air admittance valves to stop siphoning emptying the rest of the traps when water flows. Ideally imitate a modern system with a stack vented at the top and each U trapped source discharging into it and then on to you septic tank. There are rules about the vertical distance between soil (****) inlets and grey water inlets - 200mm I think. |
#8
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
George Miles posted
Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...wage-discharge -to-a-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Don't all the connections already have U-bends on them? If any don't, just add them. -- Evremonde |
#9
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
On Sunday, 17 February 2019 17:02:12 UTC, The Marquis Saint Evremonde wrote:
George Miles posted Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...wage-discharge -to-a-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Don't all the connections already have U-bends on them? If any don't, just add them. Or a HepvO https://hepvo.com/ Found them extremely good where a conventional trap might have been difficult/awkward to fit. |
#10
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
George Miles wrote:
Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...ge-discharge-t o-a-surface-water But there's a risk of foul gases coming into the house through all these new connections. Could we have extra U Bends at ground level near the new connections? Or how can it best be done? george With modern (last fifty years?) systems everything drains into a soil stack directly connected to the sewer and a single trap at each water outlet seems to work alright. Some sort of raised sewer vent near the house, and maybe anti-syphon valves on the traps is all that is needed to make the system work alright. -- Roger Hayter |
#11
Posted to uk.d-i-y
|
|||
|
|||
Connecting sinks etc to smelly septic system
On 17/02/2019 16:19, George Miles wrote:
Most of our sinks, baths, washing machines etc drain into the old rainwater system which drains we know not where. We've been told under the new regulations they must all drain into the victorian septic tank before January 2020 or we risk fines and jail. https://www.gov.uk/guidance/general-...-surface-water But there's a risk of foul gases coming into the house through all these new connections. Why? Aren't their U bends and vents already in place? Could we have extra U Bends at ground level near the new connections? Or how can it best be done? Sinkls have U bends. Wsahing machines and dishwahsers should use u bends Baths basinss and showers have U bends. Toilets have U bends WTF more do you want? Have you ever lifetd the cover off a normal mains sewage system? Foul gases ain't in it mate! george -- All political activity makes complete sense once the proposition that all government is basically a self-legalising protection racket, is fully understood. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
Connecting many low-power mains devices (wall warts etc) to single mains socket | UK diy | |||
Septic Tank Treatments (Rid-X, etc.) ? | Home Repair | |||
Bathtub, surround quandry...acrylic, fiberglass, Swanstone, Veritek, etc.etc.etc. | Home Repair | |||
Septic Tank & Cottage with 0.1 Acres - Percolation Area etc... | UK diy | |||
Wall hung bathroom sinks, lavatorys etc. | UK diy |