  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Boiler being a bellend

Vaillant ecomax 418 refuses to let any of its options be changed - and the system won't run on the default settings. When a value is adjusted you press i to back out, but it just doesn't react when a setting is adjusted. The only way out is to either press reset or +i, and either way it ignores the change just made.

Why? How to solve it?

thanks
NT






  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Boiler being a bellend

On Wednesday, 25 January 2017 17:42:43 UTC, John Rumm wrote:
On 25/01/2017 17:35, tabbypurr wrote:


Vaillant ecomax 418 refuses to let any of its options be changed -
and the system won't run on the default settings. When a value is
adjusted you press i to back out, but it just doesn't react when a
setting is adjusted. The only way out is to either press reset or +i,
and either way it ignores the change just made.

Why? How to solve it?


You may find some settings will only change in installer mode. There is
usually a way you can select a two digit installer code. Try 18


that's another thing it won't do, access the installer settings. Instructions say it's 17 but I'll try 18 too.


NT


  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Boiler being a bellend

On Wednesday, 25 January 2017 19:17:17 UTC, ARW wrote:
On 25/01/2017 17:35, tabbypurr wrote:


Vaillant ecomax 418 refuses to let any of its options be changed - and the system won't run on the default settings. When a value is adjusted you press i to back out, but it just doesn't react when a setting is adjusted. The only way out is to either press reset or +i, and either way it ignores the change just made.

Why? How to solve it?

thanks
NT






Are you saying you can alter the values but the boiler is not saving
them? If so are so remembering to save the new value by pressing the i
key until the display stops flashing?

I have made similar errors.


I can access d0 to d97. I can + & - to give new values. But then pressing i won't get me back out as it always did. I don't remember anything flashing during this process but will check again tomorrow.


NT
  #8   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Boiler being a bellend

On Wednesday, 25 January 2017 19:17:17 UTC, ARW wrote:
On 25/01/2017 17:35, tabbypurr wrote:


Vaillant ecomax 418 refuses to let any of its options be changed - and the system won't run on the default settings. When a value is adjusted you press i to back out, but it just doesn't react when a setting is adjusted. The only way out is to either press reset or +i, and either way it ignores the change just made.

Why? How to solve it?

thanks
NT


Are you saying you can alter the values but the boiler is not saving
them? If so are so remembering to save the new value by pressing the i
key until the display stops flashing?

I have made similar errors.


You got it, just needed to hold the i down awhile.

Thanks,
NT
  #9   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Boiler being a bellend

On Thursday, 26 January 2017 09:04:07 UTC, John Rumm wrote:
On 26/01/2017 01:00, tabbypurr wrote:
On Wednesday, 25 January 2017 17:42:43 UTC, John Rumm wrote:
On 25/01/2017 17:35, tabbypurr wrote:


Vaillant ecomax 418 refuses to let any of its options be changed -
and the system won't run on the default settings. When a value is
adjusted you press i to back out, but it just doesn't react when a
setting is adjusted. The only way out is to either press reset or +i,
and either way it ignores the change just made.

Why? How to solve it?

You may find some settings will only change in installer mode. There is
usually a way you can select a two digit installer code. Try 18


that's another thing it won't do, access the installer settings. Instructions say it's 17 but I'll try 18 too.


Once its been installed - one of the things you can change is the
installer code. I changed mine to 00 so I could get there without
scrolling through. So its possible yours has been changed. Fortunately
it only goes up to 99, so trying them all is doable.


thankfully it wasn't changed!

Cheers
NT
  #10   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default Boiler being a bellend

On 26/01/2017 15:27, wrote:
On Thursday, 26 January 2017 09:04:07 UTC, John Rumm wrote:
On 26/01/2017 01:00, tabbypurr wrote:
On Wednesday, 25 January 2017 17:42:43 UTC, John Rumm wrote:
On 25/01/2017 17:35, tabbypurr wrote:

Vaillant ecomax 418 refuses to let any of its options be changed -
and the system won't run on the default settings. When a value is
adjusted you press i to back out, but it just doesn't react when a
setting is adjusted. The only way out is to either press reset or +i,
and either way it ignores the change just made.

Why? How to solve it?

You may find some settings will only change in installer mode. There is
usually a way you can select a two digit installer code. Try 18

that's another thing it won't do, access the installer settings. Instructions say it's 17 but I'll try 18 too.


Once its been installed - one of the things you can change is the
installer code. I changed mine to 00 so I could get there without
scrolling through. So its possible yours has been changed. Fortunately
it only goes up to 99, so trying them all is doable.


thankfully it wasn't changed!


So was it 17 or 18 in the end?


--
Cheers,

John.

/================================================== ===============\
| Internode Ltd -
http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/


  #11   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 12,364
Default Boiler being a bellend

On Saturday, 28 January 2017 01:47:28 UTC, John Rumm wrote:
On 26/01/2017 15:27, tabbypurr wrote:
On Thursday, 26 January 2017 09:04:07 UTC, John Rumm wrote:
On 26/01/2017 01:00, tabbypurr wrote:
On Wednesday, 25 January 2017 17:42:43 UTC, John Rumm wrote:
On 25/01/2017 17:35, tabbypurr wrote:

Vaillant ecomax 418 refuses to let any of its options be changed -
and the system won't run on the default settings. When a value is
adjusted you press i to back out, but it just doesn't react when a
setting is adjusted. The only way out is to either press reset or +i,
and either way it ignores the change just made.

Why? How to solve it?

You may find some settings will only change in installer mode. There is
usually a way you can select a two digit installer code. Try 18

that's another thing it won't do, access the installer settings. Instructions say it's 17 but I'll try 18 too.

Once its been installed - one of the things you can change is the
installer code. I changed mine to 00 so I could get there without
scrolling through. So its possible yours has been changed. Fortunately
it only goes up to 99, so trying them all is doable.


thankfully it wasn't changed!


So was it 17 or 18 in the end?


17. It revealed a whole bunch of data that's not in the instruction book. Who knows what they mean.


NT
  #12   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 25,191
Default Boiler being a bellend

On 28/01/2017 01:59, wrote:
On Saturday, 28 January 2017 01:47:28 UTC, John Rumm wrote:
On 26/01/2017 15:27, tabbypurr wrote:
On Thursday, 26 January 2017 09:04:07 UTC, John Rumm wrote:
On 26/01/2017 01:00, tabbypurr wrote:
On Wednesday, 25 January 2017 17:42:43 UTC, John Rumm wrote:
On 25/01/2017 17:35, tabbypurr wrote:

Vaillant ecomax 418 refuses to let any of its options be changed -
and the system won't run on the default settings. When a value is
adjusted you press i to back out, but it just doesn't react when a
setting is adjusted. The only way out is to either press reset or +i,
and either way it ignores the change just made.

Why? How to solve it?

You may find some settings will only change in installer mode. There is
usually a way you can select a two digit installer code. Try 18

that's another thing it won't do, access the installer settings. Instructions say it's 17 but I'll try 18 too.

Once its been installed - one of the things you can change is the
installer code. I changed mine to 00 so I could get there without
scrolling through. So its possible yours has been changed. Fortunately
it only goes up to 99, so trying them all is doable.

thankfully it wasn't changed!


So was it 17 or 18 in the end?


17. It revealed a whole bunch of data that's not in the instruction book. Who knows what they mean.


With vaillant boilers there are usually a ton of settings devoted to the
vast range of control options and add ons. So for any given installation
there are usually a bunch that are not applicable.


--
Cheers,

John.

/================================================== ===============\
| Internode Ltd -
http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
outdoor temp sensor/ Boiler reset control for steam boiler? Mikepier Home Repair 12 September 29th 14 02:04 PM
combi boiler and solid fuel back boiler in tandem Phil L UK diy 2 December 4th 11 05:34 PM
Cobi boiler or regular boiler for hard-water area? Al 1953 UK diy 8 March 13th 10 04:56 PM
Help - I have a back boiler and want a combi boiler fitted but have plastic pipes! Vikki Home Repair 1 November 22nd 05 11:51 PM
Complicated central Heating; Back-Boiler and Combi-Boiler tfc715 UK diy 1 February 3rd 05 05:30 PM


All times are GMT +1. The time now is 03:31 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"