UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions.

Reply
 
LinkBack Thread Tools Search this Thread Display Modes
  #1   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 70
Default Can anyone tell me a bit about this old back boiler? Can I safely use the fireplace?



http://www.flickr.com/photos/1645502...7628151787297/

Hi.

This fireplace hasn't seen coal since 20 years ago. We would like to
put a fire in again, but wonder if there could be a problem with the
old back boiler which is still in place.

Logically, the only way gases could get out (apart from a leaking flue
which is a seperate question and check to be carried out) would be if
there was a leak inside the boiler and gasses got into the copper. As
it won't have any water in it, could the pipework be damaged by heat?

Any pointer to websited with more info would be gratefully recieved.
Yes, I have googled.

Thanks for any info you may be able to pass.

Mike.

  #2   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 43,017
Default Can anyone tell me a bit about this old back boiler? Can I safely use the fireplace?

I'd think you could melt the copper with a roaring fire if there's no
water in it.

--
*Men are from Earth, women are from Earth. Deal with it.

Dave Plowman London SW
To e-mail, change noise into sound.
  #3   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,683
Default Can anyone tell me a bit about this old back boiler? Can I safelyuse the fireplace?

Can not quite see what I am looking at, but...

Is it still plumbed in to an immersion tank, with water in it?
- If there is water in it and the whole lot freezes (cold air
descends) you can actually defrost the front half with a fire, but not
the rest and the boiling water can result in an explosion. It is rare,
but has happened - bungalows seem to be more vulnerable perhaps re
smaller chimney run when left empty.
- If there is no water in it, the fumes from the fire can be drawn
somewhere else - creating secondary fire or carbon monoxide poisoning.
This is particularly dangerous with open flue gas fires which can
create quite a bit of CO which can wander elsewhere, but other
materials burnt in a fireplace are not exempt from this fatal
scenario.

Check the chimney itself is intact and fit for usage.
- If there is a second upstairs chimney are the feathers ok (bricks
separating them), otherwise you can get gases & heat migrating.
- Likewise is the chimney fit for high temperatures created by burning
coal and that ubiquitous bit of wood that gets thrown on there,
because just about all the coal burners used to get wood in them if
coal had not been delivered. Failures in internal structure can result
in joists being set on fire.

An empty back boiler should be filled with sand completely, ideally
removed. Do not leave open pipework because products of combustion can
go somewhere else. Think the HSE has something to say on this.
  #4   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 9,188
Default Can anyone tell me a bit about this old back boiler? Can I safelyuse the fireplace?

On Nov 25, 11:17*pm, Mike Barnard
wrote:
http://www.flickr.com/photos/1645502...7628151787297/

Hi.

This fireplace hasn't seen coal since 20 years ago. We would like to
put a fire in again, but wonder if there could be a problem with the
old back boiler which is still in place.

Logically, the only way gases could get out (apart from a leaking flue
which is a seperate question and check to be carried out) would be if
there was a leak inside the boiler and gasses got into the copper. As
it won't have any water in it, could the pipework be damaged by heat?

Any pointer to websited with more info would be gratefully recieved.
Yes, I have googled.

Thanks for any info you may be able to pass.

Mike.


As long as it is still connected to the hot water cylinder and full
of water, OK to use. If empty not a good idea.
It is likely made of copper, so worth a bit these days for scrap if
removed,
As they have the actual hot water in them for your bath etc, may be
full of limescale/sludge. (ie adirect system)
  #5   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 2,024
Default Can anyone tell me a bit about this old back boiler? Can I safely use the fireplace?

On Fri, 25 Nov 2011 23:17:52 +0000, Mike Barnard
wrote:


Any pointer to websited with more info would be gratefully recieved.
Yes, I have googled.


The usual solution was to remove the pipework,fill the cast iron back
boiler with dry sand and plug the holes with fire cement. You then
drilled several holes from the fire side through the upper part of the
cast iron into the water jacket.

The boiler _must not_ be sealed otherwise there is a risk of
explosion through expansion of the air in it.

http://www.hse.gov.uk/services/local...nt/boilers.htm

Is essential reading as well as instructions on what to do.

http://www.hse.gov.uk/press/2009/coisw61109.htm
is what can happen if you don't.



  #6   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 39,563
Default Can anyone tell me a bit about this old back boiler? Can I safelyuse the fireplace?

Peter Parry wrote:
On Fri, 25 Nov 2011 23:17:52 +0000, Mike Barnard
wrote:

Any pointer to websited with more info would be gratefully recieved.
Yes, I have googled.


The usual solution was to remove the pipework,fill the cast iron back
boiler with dry sand and plug the holes with fire cement. You then
drilled several holes from the fire side through the upper part of the
cast iron into the water jacket.

The boiler _must not_ be sealed otherwise there is a risk of
explosion through expansion of the air in it.

http://www.hse.gov.uk/services/local...nt/boilers.htm

Is essential reading as well as instructions on what to do.

http://www.hse.gov.uk/press/2009/coisw61109.htm
is what can happen if you don't.

I installed a log burner that had pipes for water. I simply left them
disconnected. Didn't bother to sand fill. It is OK as I don't think the
heat exchanger was cast - its pure steel. Even if they do crack its
unlikely to put fumes in the room anyway. Chimney+fire will result in
negative pressure inside.

The sand is best practice - spreads the heat most evenly - but IME its
not essential.

Not sealing the pipes is the mandatory element .. bound to get a bit of
condensation inside and without the expansion capability, BOOM.





  #7   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 70
Default Can anyone tell me a bit about this old back boiler? Can I safely use the fireplace?


Good morning all.

Thanks for that, especially the H&S link about remaing water building
up steam. We've decided to pull the lot out. Now I need links on how
to rebuild a proper fireplace!
  #8   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 39,563
Default Can anyone tell me a bit about this old back boiler? Can I safelyuse the fireplace?

Mike Barnard wrote:
Good morning all.

Thanks for that, especially the H&S link about remaing water building
up steam. We've decided to pull the lot out. Now I need links on how
to rebuild a proper fireplace!


That is not hard..but the chimney and flue are.

The key is that the aperture of the fire should be no more than 5-7
times the cross section of the flue, and its NOT a good idea to have a
flat topped fire box with a hole in it - you need a smoke chamber above
the lintel for an open fire.

If that hearth was designed for a stove, you may need a smoke hood if
you are going open hearth


If you go for a stove, then you should probably line the flue.

If the fire has been out of action for years, please do a smoke test and
look in the loft for signs of busted mortar joints: round here with old
flues and timber frames,, after electrical this is the most common place
for fires to start. Consider a loft mounted smoke alarm as well.


  #9   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,307
Default Can anyone tell me a bit about this old back boiler? Can I safely use the fireplace?

Mike Barnard wrote:

Good morning all.

Thanks for that, especially the H&S link about remaing water building
up steam. We've decided to pull the lot out. Now I need links on how
to rebuild a proper fireplace!


I did just the same when we moved here.
Ours was a large copper cylinder set into the fireplace. Jemmy it out,
(and weigh it in), then you fill in the holes with firebricks/bits of
fire bricks with lime cement.
You then put you fireback into position, it may need lifting up etc,
then fill the back, again with a mix of firebrick, or, plain lime
cement/mortar.I think there may have been some refractory insulation in
there too.
Let that go off, then fill all gaps with mortar.
There may be bits I've missed as it was 15 years ago when I did mine.
I got a book from the library that showed exactly how it was done
(surely there is a step by step website now?), and it has lasted well,
the fireback has started to wear out a little at the bottom, otherwise,
the chimney sweep says it is all good.

Alan.
--
To reply by e-mail, change the ' + ' to 'plus'.
  #10   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 816
Default Can anyone tell me a bit about this old back boiler? Can I safely use the fireplace?

In message , Mike Barnard
writes

Good morning all.

Thanks for that, especially the H&S link about remaing water building
up steam. We've decided to pull the lot out. Now I need links on how
to rebuild a proper fireplace!

Very wise decision.
--
hugh


  #11   Report Post  
Posted to uk.d-i-y
external usenet poster
 
Posts: 1,683
Default Can anyone tell me a bit about this old back boiler? Can I safelyuse the fireplace?

On Nov 26, 11:02*am, (A.Lee) wrote:
I think there may have been some refractory insulation in there too.


Vermiculite.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Sorry back to the fireplace problems [email protected] Home Ownership 5 March 3rd 06 05:11 PM
Help - I have a back boiler and want a combi boiler fitted but have plastic pipes! Vikki Home Repair 1 November 22nd 05 11:51 PM
Complicated central Heating; Back-Boiler and Combi-Boiler tfc715 UK diy 1 February 3rd 05 05:30 PM
DIY fireplace back-board using tiles... N. Thornton UK diy 8 December 9th 04 02:32 PM
Surface for back of open fireplace Robert Irwin UK diy 7 June 7th 04 10:01 AM


All times are GMT +1. The time now is 11:18 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"