Before starting to fit a new kitchen, the fitter turned off the CH+HW,
then disconnected and bypassed the kitchen sink.
We were out last evening, but the heating didn't switch on this
morning, which has me concerned.
Another point, I left the thermostat on ~15degC overnight and the
heating on; around midnight, there were strange gurgling noises
compeletely unlike anything I've heard before from the system, so I
just turned everything off and went back to bed.
I'm waiting for the fitter to arrive this morning, so I can find out
what sequence he followed, but what I've tried is:
- ensuring the stop-cock that feeds the pump is fully open
- starting up the HW and CH independently (we've had issues before
where HW would come on and not the CH, but it's been fine for a while
and wouldn't want it to become a red herring)
- turning up the wall thermostat to max

I can hear the pump chrning away, but no change has resulted, the
system doesn't appear to be heating up either water or rads.
Boiler is in the garage, soI'll go out and check it's lit when I've
written this, but can't see that being the likely problem.

Could an air-lock have been introduced when the fitter turned off the
system initially ?
  #2   Report Post  
David W.E. Roberts
 
Posts: n/a
Default CH not starting after switch-off


"KTS" wrote in message
om...
Before starting to fit a new kitchen, the fitter turned off the CH+HW,
then disconnected and bypassed the kitchen sink.
We were out last evening, but the heating didn't switch on this
morning, which has me concerned.
Another point, I left the thermostat on ~15degC overnight and the
heating on; around midnight, there were strange gurgling noises
compeletely unlike anything I've heard before from the system, so I
just turned everything off and went back to bed.
I'm waiting for the fitter to arrive this morning, so I can find out
what sequence he followed, but what I've tried is:
- ensuring the stop-cock that feeds the pump is fully open
- starting up the HW and CH independently (we've had issues before
where HW would come on and not the CH, but it's been fine for a while
and wouldn't want it to become a red herring)
- turning up the wall thermostat to max

I can hear the pump chrning away, but no change has resulted, the
system doesn't appear to be heating up either water or rads.
Boiler is in the garage, soI'll go out and check it's lit when I've
written this, but can't see that being the likely problem.

Could an air-lock have been introduced when the fitter turned off the
system initially ?


Combi boiler (no header tank)?
Traditional (hot water cylinder, header tank)?
What kind of system is it?


  #3   Report Post  
Roger Mills
 
Posts: n/a
Default CH not starting after switch-off


"KTS" wrote in message
om...
Before starting to fit a new kitchen, the fitter turned off the CH+HW,
then disconnected and bypassed the kitchen sink.
We were out last evening, but the heating didn't switch on this
morning, which has me concerned.
Another point, I left the thermostat on ~15degC overnight and the
heating on; around midnight, there were strange gurgling noises
compeletely unlike anything I've heard before from the system, so I
just turned everything off and went back to bed.
I'm waiting for the fitter to arrive this morning, so I can find out
what sequence he followed, but what I've tried is:
- ensuring the stop-cock that feeds the pump is fully open
- starting up the HW and CH independently (we've had issues before
where HW would come on and not the CH, but it's been fine for a while
and wouldn't want it to become a red herring)
- turning up the wall thermostat to max

I can hear the pump chrning away, but no change has resulted, the
system doesn't appear to be heating up either water or rads.
Boiler is in the garage, soI'll go out and check it's lit when I've
written this, but can't see that being the likely problem.

Could an air-lock have been introduced when the fitter turned off the
system initially ?


Are you sure that the fitter hasn't turned off the GAS supply? The pump and
stats would still work - but the boiler would churn out COLD water!

Roger


  #4   Report Post  
KTS
 
Posts: n/a
Default CH not starting after switch-off

"David W.E. Roberts" wrote in message ...

Combi boiler (no header tank)?
Traditional (hot water cylinder, header tank)?
What kind of system is it?


Sorry, was in a hurry to post !

Yes, it is a traditional gravity pump system.
Installed 2001 by the wonderful BG.
Boiler is BG-branded F2 (Potterton?).

In answer to the other post, the gas supply definitely wasn't switched
off.

Update:
-------

Gets more bizarre. I thought it would be unlikely to be the boiler,
but when I eventually went to take a look, the boiler had switched off
(boiler is in garage).
The boiler has an Overheat Limit Thermostat, which appeared to have
tripped. I had to reset it by pressing a recessed button on the
underside of the boiler casing.
By resetting this thermostat, and powering the boiler off and on
again, I managed to get it to light. This worked fine for the rest of
the day, and we had heating and HW throughout.
Overnight, however, the system wouldn't switch on at the programmed
time. Had a look at the boiler again this morning, same story - it had
switched itself off.
Same procedure sa yesterday lit the boiler temporarily, but the CH+HW
wouldn't get going. The boiler also cuts out after a few minutes, with
quite loud spluttering and banging.
The pump+valve are in the airing cupboard above thestairwell, along
with the HW cylinder. When I switch either function on, there is a low
grinding noise for about 45 secs, then a constant very low rumble for
the next few minutes, then silence. Looks like the pump is trying to
turn itself over, but can't.

Any help please, or is it best to have someone in to look at it ?
Can't really do w/o CH with the kids at home.
  #5   Report Post  
Roger Mills
 
Posts: n/a
Default CH not starting after switch-off


"KTS" wrote in message
om...
"David W.E. Roberts" wrote in message

...

Combi boiler (no header tank)?
Traditional (hot water cylinder, header tank)?
What kind of system is it?


Sorry, was in a hurry to post !

Yes, it is a traditional gravity pump system.
Installed 2001 by the wonderful BG.
Boiler is BG-branded F2 (Potterton?).

In answer to the other post, the gas supply definitely wasn't switched
off.

Update:
-------

Gets more bizarre. I thought it would be unlikely to be the boiler,
but when I eventually went to take a look, the boiler had switched off
(boiler is in garage).
The boiler has an Overheat Limit Thermostat, which appeared to have
tripped. I had to reset it by pressing a recessed button on the
underside of the boiler casing.
By resetting this thermostat, and powering the boiler off and on
again, I managed to get it to light. This worked fine for the rest of
the day, and we had heating and HW throughout.
Overnight, however, the system wouldn't switch on at the programmed
time. Had a look at the boiler again this morning, same story - it had
switched itself off.
Same procedure sa yesterday lit the boiler temporarily, but the CH+HW
wouldn't get going. The boiler also cuts out after a few minutes, with
quite loud spluttering and banging.
The pump+valve are in the airing cupboard above thestairwell, along
with the HW cylinder. When I switch either function on, there is a low
grinding noise for about 45 secs, then a constant very low rumble for
the next few minutes, then silence. Looks like the pump is trying to
turn itself over, but can't.

Any help please, or is it best to have someone in to look at it ?
Can't really do w/o CH with the kids at home.


Almost certainly a dodgy pump - which runs once it gets started, but
sometimes fails to run at all.

If the pump fails, the boiler WILL trip - because the heated water isn't
being removed from it. It turns its burner off with the normal thermostat,
but the residual heat in the metal parts continues to heat the water to an
unacceptable temperature - whereupon the overheat stat trips.

Some pumps have an end cap which you can remove termporarily (with very
little loss of water) behind which is the end of the shaft. You can see
whether this is rotating, and give it a nudge with a screwdriver if it is
stuck. This sometimes gets it going again - but if this happens often,
you'll need to replace the pump.

Roger


Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Dimmer Switch Advice Chris Spyrou UK diy 0 October 6th 03 07:13 PM
Wiring a 3 way light switch. Mike Hibbert UK diy 8 October 3rd 03 06:51 PM
Fridges: weird "fast freeze" switch The Question Asker UK diy 9 August 12th 03 04:55 PM


All times are GMT +1. The time now is 10:58 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"