John Stumbles July 16th 07 09:02 PM

Accesibility of crimped/soldered cable joints?
 
Can anybody quote references from BS7671 or the OSG that says that crimped
or soldered cable joints do NOT have to be accessible for inspection?

(Something that came up in my CG2381 training today.)

--
John Stumbles

Fundamentalist agnostic

John Rumm July 16th 07 09:21 PM

Accesibility of crimped/soldered cable joints?
 
John Stumbles wrote:
Can anybody quote references from BS7671 or the OSG that says that crimped
or soldered cable joints do NOT have to be accessible for inspection?

(Something that came up in my CG2381 training today.)


"526-04 Accessibility of connections

526-04-01 Except for the following, every connection and joint shall be
accessible for inspection, testing and maintenance:

(i) a compound-filled or encapsulated joint
(ii) a connection between a cold tail and a heating element (e.g. a
ceiling and floor heating system, a pipe traceheating system)
(iii) a joint made by welding, soldering, brazing or compression tool
(iv) a joint forming part of the equipment complying with the
appropriate product standard."


Part (iii) is the bit you are after.





--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/

John Stumbles July 16th 07 10:36 PM

Accesibility of crimped/soldered cable joints?
 
On Mon, 16 Jul 2007 21:21:13 +0100, John Rumm wrote:

"526-04 Accessibility of connections


OK thanks, just found that myself. I'll ask the gaffer tomorrow.

How about putting that reference in the wiki article?

--
John Stumbles

Fundamentalist agnostic

John Rumm July 16th 07 11:02 PM

Accesibility of crimped/soldered cable joints?
 
John Stumbles wrote:
On Mon, 16 Jul 2007 21:21:13 +0100, John Rumm wrote:

"526-04 Accessibility of connections


OK thanks, just found that myself. I'll ask the gaffer tomorrow.

How about putting that reference in the wiki article?


Done!

--