Golan November 21st 06 02:58 AM

BG was in my house and installed a room thermostat
 
BG was in my house and installed a room thermostat to my combi boiler
worcester24CDi combi. For the last 4 days I am trying to work with it
but the thermostat act weird. Lets say the house get worm and I click
it off. On 21 degrees it will not click back on not even in the morning
after. Like as if it not sensitive enough. I read here about the fact
that there is an anticipator in the thermostat that make it think it is
1.5 degree wormer and that's what make the thermostat more sensitive.
Is it true?

After check the wires I see that the guy connects only 2 wires and did
not connect the N which mean the anticipator will not function. This is
the model of thermostat that I have (RTS1)
http://www.wholesaleheating.co.uk/techfiles/302050.html

And more info here
http://www.invensyscontrolseurope.co...RTS_Dsheet.pdf


I don't know if it have an anticipator in it. And if I will connect
the N will it help and make it more sensitive?
Dose some one have that thermostat and can tell me?

Many Thanks


John Rumm November 21st 06 04:19 AM

BG was in my house and installed a room thermostat
 
Golan wrote:

And more info here
http://www.invensyscontrolseurope.co...RTS_Dsheet.pdf


I don't know if it have an anticipator in it. And if I will connect
the N will it help and make it more sensitive?


It looks like an elctromechanical type stat and has a neutral connection
so there is a very strong likelihood that it has a compensator and will
function better with a neutral. The lackluster performance you are
getting would also suggest this.

Failing that fit a modern programmable stat that will work well without
a neutral. e.g.:

http://www.screwfix.com/app/sfd/cat/...17585&ts=82132

--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/

Dave Plowman (News) November 21st 06 09:00 AM

BG was in my house and installed a room thermostat
 
In article om,
Golan wrote:
BG was in my house and installed a room thermostat to my combi boiler
worcester24CDi combi. For the last 4 days I am trying to work with it
but the thermostat act weird. Lets say the house get worm and I click
it off. On 21 degrees it will not click back on not even in the morning
after. Like as if it not sensitive enough. I read here about the fact
that there is an anticipator in the thermostat that make it think it is
1.5 degree wormer and that's what make the thermostat more sensitive.
Is it true?


After check the wires I see that the guy connects only 2 wires and did
not connect the N which mean the anticipator will not function.


Correct. Get BG back to do the job properly. This means either installing
a three wire circuit or changing the thermostat for a solid state type
which doesn't need a heater coil.

--
*'ome is where you 'ang your @ *

Dave Plowman London SW
To e-mail, change noise into sound.

Golan November 21st 06 12:39 PM

BG was in my house and installed a room thermostat
 

John Rumm wrote:
Golan wrote:

And more info here
http://www.invensyscontrolseurope.co...RTS_Dsheet.pdf


I don't know if it have an anticipator in it. And if I will connect
the N will it help and make it more sensitive?


It looks like an elctromechanical type stat and has a neutral connection
so there is a very strong likelihood that it has a compensator and will
function better with a neutral. The lackluster performance you are
getting would also suggest this.

Failing that fit a modern programmable stat that will work well without
a neutral. e.g.:

http://www.screwfix.com/app/sfd/cat/...17585&ts=82132

--
Cheers,

John.

/================================================== ===============\
| Internode Ltd - http://www.internode.co.uk |
|-----------------------------------------------------------------|
| John Rumm - john(at)internode(dot)co(dot)uk |
\================================================= ================/


so if i get one of the digital ones i dont need to wire the neutral at
all ??


Dave Plowman (News) November 21st 06 01:34 PM

BG was in my house and installed a room thermostat
 
In article .com,
Golan wrote:
so if i get one of the digital ones i dont need to wire the neutral at
all ??


If battery operated, no.

--
*If you can't see my mirrors, I'm doing my hair*

Dave Plowman London SW
To e-mail, change noise into sound.

Golan November 22nd 06 01:29 AM

BG was in my house and installed a room thermostat
 

Dave Plowman (News) wrote:
In article .com,
Golan wrote:
so if i get one of the digital ones i dont need to wire the neutral at
all ??


If battery operated, no.

--
*If you can't see my mirrors, I'm doing my hair*

Dave Plowman London SW
To e-mail, change noise into sound.


What about thet one. is is 2 wire ????

http://www.heatingcontrolsonline.co....products_id=63


Andy Burns November 22nd 06 08:43 AM

BG was in my house and installed a room thermostat
 
Golan wrote:

What about thet one. is is 2 wire ????
http://www.heatingcontrolsonline.co....products_id=63


The manual on that page shows that it has a C/O relay as output, and is
battery powered, so yes ...

[email protected] November 22nd 06 10:11 AM

BG was in my house and installed a room thermostat
 
Golan wrote:

BG was in my house and installed a room thermostat to my combi boiler
worcester24CDi combi. For the last 4 days I am trying to work with it
but the thermostat act weird. Lets say the house get worm and I click
it off. On 21 degrees it will not click back on not even in the morning
after. Like as if it not sensitive enough. I read here about the fact
that there is an anticipator in the thermostat that make it think it is
1.5 degree wormer and that's what make the thermostat more sensitive.
Is it true?


yup. its a compensation resistor.

After check the wires I see that the guy connects only 2 wires and did
not connect the N which mean the anticipator will not function. This is
the model of thermostat that I have (RTS1)
http://www.wholesaleheating.co.uk/techfiles/302050.html

And more info here
http://www.invensyscontrolseurope.co...RTS_Dsheet.pdf


I don't know if it have an anticipator in it. And if I will connect
the N will it help and make it more sensitive?
Dose some one have that thermostat and can tell me?

Many Thanks


all points correct. Except your decision to let BG near your gas
install.


NT


Dave Plowman (News) November 22nd 06 10:24 AM

BG was in my house and installed a room thermostat
 
In article .com,
Golan wrote:

Dave Plowman (News) wrote:
In article .com,
Golan wrote:
so if i get one of the digital ones i dont need to wire the neutral
at all ??


If battery operated, no.


What about thet one. is is 2 wire ????


http://www.heatingcontrolsonline.co....products_id=63


It says it is in the first paragraph of the description. ;-)

--
*The early bird gets the worm, but the second mouse gets the cheese *

Dave Plowman London SW
To e-mail, change noise into sound.