Home |
Search |
Today's Posts |
![]() |
|
UK diy (uk.d-i-y) For the discussion of all topics related to diy (do-it-yourself) in the UK. All levels of experience and proficency are welcome to join in to ask questions or offer solutions. |
Reply |
|
LinkBack | Thread Tools | Display Modes |
|
#1
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Hello Everyone,
I am about to purchase one of these: http://www.jaksch-kuechentechnik.de/mobil.htm Which both come with a standard german plug fitting. The smaller model (A2000) is 10-16amp, 2200w, so would appear to be fine to replace with a 13amp plug and connect to any socket in my house. The larger model (A4000) says 16amp 3200w, so this sounds like too much for standard UK wiring. As you can probably tell, I know very little about all this so would appreciate some advice. The link above has some power rating information in it, ok it's in german, but hopefully someone will be able to advise... thanks in advance. dan. |
#3
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
The larger model (A4000) says 16amp 3200w, so this sounds like too much
for standard UK wiring. It will need to be fitted to a dedicated 16A circuit from the consumer unit. It could either be hard wired, with the plug cut off, or you could fit a 16A Schuko outlet. You probably shouldn't wire it up to a ring circuit. This is because (a) it would not be protected at 16A like it expects and (b) it could easily unbalance the ring circuit. Christian. |
#4
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
"Christian McArdle" writed in
: The larger model (A4000) says 16amp 3200w, so this sounds like too much for standard UK wiring. It will need to be fitted to a dedicated 16A circuit from the consumer unit. It could either be hard wired, with the plug cut off, or you could fit a 16A Schuko outlet. Is this permitted under the new (?part P?) regulations? |
#5
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
On 11 Jul 2006 05:17:35 -0700 someone who may be
wrote this:- I am about to purchase one of these: http://www.jaksch-kuechentechnik.de/mobil.htm The larger model (A4000) says 16amp 3200w, so this sounds like too much for standard UK wiring. Do you want to move it around? If so, where do you want to move it between? If you want to move it around then the way to do this would be with dedicated circuit(s). The socket(s) could be a 16A Schuko or BS4343. If only one appliance is going to be plugged in then multiple sockets could be wired radially. With the Schuko you would need a 16A MCB, with the other you might be able to convince yourself that a 20A fuse or MCB is an appropriate protective device. If you don't want to move it around you could wire it to a fixed outlet. Ideally this would still be via a dedicated circuit. However, if you have a suitable ring circuit then you might be able to convince yourself that it can be wired to that, protected by a local 16A MCB. Suitable would certainly include that the ring is not already heavily loaded. -- David Hansen, Edinburgh I will *always* explain revoked encryption keys, unless RIP prevents me http://www.opsi.gov.uk/acts/acts2000/00023--e.htm#54 |
#6
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]() wrote: Hello Everyone, I am about to purchase one of these: http://www.jaksch-kuechentechnik.de/mobil.htm Which both come with a standard german plug fitting. The smaller model (A2000) is 10-16amp, 2200w, so would appear to be fine to replace with a 13amp plug and connect to any socket in my house. The larger model (A4000) says 16amp 3200w, so this sounds like too much for standard UK wiring. Hmmm......... What is this thing exactly? It looks a bit like a portable hob/griddle with 2 separate heatng zones. My feeling would be that the 3200W is the maximum it could possibly draw flat out. In practice, this isn't going to happen. I suspect that if you cut off the plug and fitted a good quality 13A plug with 13A fuse, and used it only on lightly loaded circuits, you wouldn't have any problems. Though if it is only going to be used in one location, then I would be tempted to go for either a dedicated 13A socket on it's own circuit, or preferably a fused connection unit. Not saying you should do it this way, but I think it would be fine. |
#7
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]() |
#8
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]()
Thanks Everyone!
I think you've all pretty much summed up what I suspected, i.e. that this will probably work fine with a 13a plug, but to do it properly/safely I should have a dedicated circuit, 16a plug/socket etc. I might just go for the smaller model which is definitely OK for 13a, although this will no doubt limit my culinary horizons.... Dan. |
#9
![]()
Posted to uk.d-i-y
|
|||
|
|||
![]() Hmmm......... What is this thing exactly? it's a portable Teppan Yaki grill, like they have in Japanese restaurants where the chef cooks the food in front of you and generally ponces about with it. My feeling would be that the 3200W is the maximum it could possibly draw flat out. In practice, this isn't going to happen. indeed. I suspect that if you cut off the plug and fitted a good quality 13A plug with 13A fuse, and used it only on lightly loaded circuits, you wouldn't have any problems. it is tempting...! Dan. |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
Recomendation for kitchen | UK diy | |||
Routing laundry drain to kitchen drain possible? | Home Repair | |||
Cabinet Design Centre v7.0 - Cubit, 20-20 Kitchen Design V6.1,CabinetVision Solid, Planit Millennium II [2 CDs], TurboCAD Pro V9.0 [3 CDs] (Turbocad Pro V9.0, TurboCad Deluxe 9.2 FloorPlan v7.3, TurboProjectExpress v4S), Big Hammer Do It Yourself (De | Home Ownership | |||
Planit Millennium II [2 CDs] new !, and other Kitchen Design 3D programscheap software for fitted kitchen design | Woodworking | |||
Kitchen Fitter Standards | UK diy |