  #1   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 101
Default battery backed up Fluorescent lighting

Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.

Thanks
  #3   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 4,228
Default battery backed up Fluorescent lighting


wrote in message
...
Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.

Thanks


Many of them will have a seperate ballast for the two outside tubes. The
center tube will have its own ballast with an internal battery. There is
usually a connector between two of that ballast wires that will disconnect
the internal battery. I do not recall if it will still let the ballast work
as a normal ballast.

If not, you will have to replace that center ballast with a single tube
ballast, or maybe a newer electronic type that will operate the 3 bulbs and
do away with the other two tube ballast.


  #4   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 101
Default battery backed up Fluorescent lighting

On Oct 7, 4:27*pm, RBM wrote:
On 10/7/2011 6:59 PM, wrote:

Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.


Thanks


Open them up, remove the battery backup module and follow the wiring
diagram that will be on the ballast transformer


If I disconnect power to the fixture, will the battery module wires
still have 220V on them? I want to avoid a shock when disconnecting
the battery module.
  #5   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 3,236
Default battery backed up Fluorescent lighting

On Oct 7, 6:48*pm, "Ralph Mowery" wrote:
wrote in message

...

Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.


Thanks


Many of them will have a seperate ballast for the two outside tubes. *The
center tube will have its own ballast with an internal battery. *There is
usually a connector between two of that ballast wires that will disconnect
the internal battery. *I do not recall if it will still let the ballast work
as a normal ballast.

If not, you will have to replace that center ballast with a single tube
ballast, or maybe a newer electronic type that will operate the 3 bulbs and
do away with the other two tube ballast.


My guess is that the center bulb is the only one that is supposed to
light up in case there is a failure. The theory is that a single bulb
lighting up will provide sufficient lighting for emergency uses, such
as to evacuate people, find ddoorways, etc.. So, there may be nothing
wrong with the ballast for the center tube. Most fixtures will have a
manufacturer's name on them somewhere, ballasts also always have some
ID on them. That is where you should start.

The center tube may be run by both a separate ballast and the battery
back-up. You mention 220V, are youo not in the USA?


  #7   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default battery backed up Fluorescent lighting

Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.


Thanks


Open them up, remove the battery backup module and follow the wiring
diagram that will be on the ballast transformer


If I disconnect power to the fixture, will the battery module wires
still have 220V on them? I want to avoid a shock when disconnecting
the battery module.


*Yes there will be power coming out of the battery pack once it has been
disconnected. Usually there is a disconnect for the battery by means of a
wire connection. You may see two wires joined together with factory
terminals. Just separate them and it will kill the battery output. It may
be near the test button. As RBM stated, look at the wiring diagram on the
battery and the ballast.

  #8   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,934
Default battery backed up Fluorescent lighting

Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.


Thanks


Open them up, remove the battery backup module and follow the wiring
diagram that will be on the ballast transformer


If I disconnect power to the fixture, will the battery module wires
still have 220V on them? I want to avoid a shock when disconnecting
the battery module.


*Yes there will be power coming out of the battery pack once it has been
disconnected. Usually there is a disconnect for the battery by means of a
wire connection. You may see two wires joined together with factory
terminals. Just separate them and it will kill the battery output. It
may be near the test button. As RBM stated, look at the wiring diagram on
the battery and the ballast.



*BTW the battery is there to provide egress lighting when the power goes
out. This is usually a code requirement. The center tube lighting at half
brightness is normal. It is suppose to provide just enough light to exit
the building. The battery back up does not light up all of the tubes.

If you want to be able to shut the fixtures off without the batteries
activating, you need to provide a separate, unswitched feed to those
batteries from the same circuit.

  #11   Report Post  
Posted to alt.home.repair
external usenet poster
 
Posts: 1,106
Default battery backed up Fluorescent lighting

On Oct 7, 6:59*pm, " wrote:
Our office has some battery backed up Fluorescent lighting that no
longer work. Each lighting fixture has three 4' Fluorescent tubes.
When the red button is pressed, the center tube will light up, so it
seems to indicate that power is present. Is the ballast bad or
something? How to convert these battery backed up Fluorescent lighting
fixtures to be the normal kinds which is on a switched circuit? We
want them to be off when power is cut.

Thanks


Do you own your office ?

Is there a code requirement for the battery backed up lighting ?

Ask your landlord what the possible alternative options are for
the back up lighting, those fixtures cost more than standard
ones so they wouldn't be there if they weren't required...

Make sure your rental agreement allows you to reconfigure
the lighting and then if you were allowed to do so you would
have to hire on a licensed electrician to do that work, office
type modifications are not DIY projects...

~~ Evan
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Battery-backed sump pumps Robert Green Home Repair 11 May 20th 08 03:45 PM
Basement Watchdog redundant battery backed sump pump- thumbs up Todd H. Home Repair 16 October 4th 06 09:24 PM
Fluorescent lighting Sponix UK diy 0 February 7th 06 03:27 PM
Repairing a K2000R synthesizer: battery backed memory Robert Graham Jr. Electronics Repair 2 February 16th 05 12:57 AM
fluorescent lighting stuart noble UK diy 17 October 15th 04 10:25 PM


All times are GMT +1. The time now is 12:55 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"