[email protected] October 25th 07 05:50 AM

Electrical Wiring
 
I plan to bring power to my garage's sub-panel from a sub-panel at the
pump house. The garage is situated on a rock built-up base/fill. My
question is what is the burial requirements at the garage base/fill
and at the flat area between the garage and the pump house. I
understand that code is 18" with PVC. But that would be hard to do at
the garage base/fill. Would Sch 80 PVC require less cover? Any
suggestions. Thanks.


Chris Friesen October 25th 07 06:33 AM

Electrical Wiring
 
wrote:
My
question is what is the burial requirements at the garage base/fill
and at the flat area between the garage and the pump house. I
understand that code is 18" with PVC. But that would be hard to do at
the garage base/fill.


If underground is difficult, have you considered going with an overhead
line?

Chris

RBM October 25th 07 12:15 PM

Electrical Wiring
 
Galv pipe, 6" or cover the pvc with 2" concrete



wrote in message
oups.com...
I plan to bring power to my garage's sub-panel from a sub-panel at the
pump house. The garage is situated on a rock built-up base/fill. My
question is what is the burial requirements at the garage base/fill
and at the flat area between the garage and the pump house. I
understand that code is 18" with PVC. But that would be hard to do at
the garage base/fill. Would Sch 80 PVC require less cover? Any
suggestions. Thanks.




John Grabowski October 25th 07 12:45 PM

Electrical Wiring
 

wrote in message
oups.com...
I plan to bring power to my garage's sub-panel from a sub-panel at the
pump house. The garage is situated on a rock built-up base/fill. My
question is what is the burial requirements at the garage base/fill
and at the flat area between the garage and the pump house. I
understand that code is 18" with PVC. But that would be hard to do at
the garage base/fill. Would Sch 80 PVC require less cover? Any
suggestions. Thanks.


You can use rigid galvanized pipe at 6" unless it goes under a driveway. In
that case it would have to be 18".


Steve Barker[_3_] October 25th 07 05:00 PM

Electrical Wiring
 
Is there a permit involved? Or any other chance of do gooders intervention?

s


wrote in message
oups.com...
I plan to bring power to my garage's sub-panel from a sub-panel at the
pump house. The garage is situated on a rock built-up base/fill. My
question is what is the burial requirements at the garage base/fill
and at the flat area between the garage and the pump house. I
understand that code is 18" with PVC. But that would be hard to do at
the garage base/fill. Would Sch 80 PVC require less cover? Any
suggestions. Thanks.