Default wiring for electric water heater

Hi,

This is a noob question and I wonder if there's any qualified wireman
around to answer my question. I have just fixed up a water heater but
because there was no existing power points in the bathroom, the wireman
fixed one up which was extended from the power socket in my room. It
was a bit of a hassle to take the power from the main because a lot of
drilling has to be done and this is just a rented place. I figure I
could live with that. Only thing is that he asked me not to use the
air-cond together with the heater at the same time. The water heater
also has built in ELCB. Now my question is whether are there any
dangers involved with the current scenario? My father is a bit paranoid
because he asked for a second opinion from a qualified wireman and he
said he knew of a couple who was electrocuted recently because the
heater switch was not taken from the main point. I hope I can get an
opinion from this newsgroup. I apologize if I'm not clear enough as I
don't really know the proper terms to use. Thanks in advance.

Ken

  #2   Report Post  
Posted to alt.home.repair
Joseph Meehan
 
Posts: n/a
Default wiring for electric water heater

Ken wrote:
Hi,

This is a noob question and I wonder if there's any qualified wireman
around to answer my question. I have just fixed up a water heater but
because there was no existing power points in the bathroom, the
wireman fixed one up which was extended from the power socket in my
room. It was a bit of a hassle to take the power from the main
because a lot of drilling has to be done and this is just a rented
place. I figure I could live with that. Only thing is that he asked
me not to use the air-cond together with the heater at the same time.
The water heater also has built in ELCB. Now my question is whether
are there any dangers involved with the current scenario?


My father
is a bit paranoid because he asked for a second opinion from a
qualified wireman and he said he knew of a couple who was
electrocuted recently because the heater switch was not taken from
the main point.


That story is likely a misinterpretation of the facts. Properly wired
there would be no difference is safety either way.

I hope I can get an opinion from this newsgroup. I
apologize if I'm not clear enough as I don't really know the proper
terms to use. Thanks in advance.

Ken


Personally I would not have allowed it done that way. I would have paid
the difference and had it done right by putting in a dedicated circuit.

I have not checked, but I would not be surprised to find out that code
requires it to be on a dedicated circuit. You might check the instructions
that came with the heater. In any case I believe it is at best sloppy work.
The dead giveaway was "he asked me not to use the air-cond together with the
heater at the same time."



--
Joseph Meehan

Dia duit


  #3   Report Post  
Posted to alt.home.repair
RBM
 
Posts: n/a
Default wiring for electric water heater

It sounds like a small heater and probably uses the same amperage and
voltage that the air uses. Clearly if both were used at the same time it
would overload the circuit and should trip the breaker. What he should have
done to make it safe, is install a single pole double throw switch (assuming
it's 120 volt) in the circuit which would allow current to ONLY go to either
the airconditioner or the heater at one time.


"Ken" wrote in message
oups.com...
Hi,

This is a noob question and I wonder if there's any qualified wireman
around to answer my question. I have just fixed up a water heater but
because there was no existing power points in the bathroom, the wireman
fixed one up which was extended from the power socket in my room. It
was a bit of a hassle to take the power from the main because a lot of
drilling has to be done and this is just a rented place. I figure I
could live with that. Only thing is that he asked me not to use the
air-cond together with the heater at the same time. The water heater
also has built in ELCB. Now my question is whether are there any
dangers involved with the current scenario? My father is a bit paranoid
because he asked for a second opinion from a qualified wireman and he
said he knew of a couple who was electrocuted recently because the
heater switch was not taken from the main point. I hope I can get an
opinion from this newsgroup. I apologize if I'm not clear enough as I
don't really know the proper terms to use. Thanks in advance.

Ken



  #4   Report Post  
Posted to alt.home.repair
Speedy Jim
 
Posts: n/a
Default wiring for electric water heater

Ken wrote:
Hi,

This is a noob question and I wonder if there's any qualified wireman
around to answer my question. I have just fixed up a water heater but
because there was no existing power points in the bathroom, the wireman
fixed one up which was extended from the power socket in my room.


SNIP

Sounds like you ought to post to this group:

UK.D-I-Y

Jim
  #5   Report Post  
Posted to alt.home.repair
Ken
 
Posts: n/a
Default wiring for electric water heater

Thanks for the replies.....the heater that i'm using is a Pensonic
PWH767E. The power rating on the box says 3.6Kw 15A, 240 a.c.
50Hz....not sure if the info helps....I don't know if it's a small or
big heater. Anyway the problem isn't with the air-cond, I never and
don't plan to use the air-cond. That socket is purely meant for the
water heater and also my desktop computer. I'm also willing to turn off
my computer while the heater is on. So would that have any risk and
danger of electrocution? The water heater also comes with built-in
ELCB. Wouldn't the most that would happen be that the main switch be
tripped and besides that....there's also ELCB protection. How dangerous
is the electrocution part?

I'm just wondering if my father is being worried for no reason. I do
plan to have it fixed to the main power later but only when I'm free.
So for now should I stop using it because of this concern?



  #6   Report Post  
Posted to alt.home.repair
 
Posts: n/a
Default wiring for electric water heater

The electrocution risk has nothing to do with it being on a shared
circuit with the air conditioner. Electrocution risk comes if it is
miswired, has a reversed hot, neutral, ground, etc. However, this is a
pretty dumb way to wire this up. Who wants to figure out when to heat
water, vs when to turn on the air conditioner, etc? He should have
been able to put this on either it's own circuit or another circuit
without a large load like the AC. If you can live with the
incovenience and it is otherwise done correctly, there is no
elecrocution risk different from any other outlet.

  #7   Report Post  
Posted to alt.home.repair
Ken
 
Posts: n/a
Default wiring for electric water heater

Thanks for the reply......i've uploaded some pics to give a better
idea. He stated that it takes a lot of work to connect to the
main...maybe have to go through the roof and all the way downstairs.
I'm staying in a double-storey terrace house. So he said it's easier to
get it from my room which has the attached bathroom. What bout the
story about the electrocuted couple that I heard from my father.
They've also done the same thing......dragged from the room socket. So
it's basically miswired for that case?


this is the socket in my room where it's being extended from
http://i83.photobucket.com/albums/j2...05-06_2358.jpg

this is the water heater switch in the bathroom
http://i83.photobucket.com/albums/j2...05-06_2356.jpg

and this is the water heater
http://i83.photobucket.com/albums/j2...05-06_2357.jpg

  #8   Report Post  
Posted to alt.home.repair
 
Posts: n/a
Default wiring for electric water heater

Well, it sure looks like hell. For me to have had it done that way I
would have to have been convinced that it was going to cost a lot more
to put it on it's own circuit with most of the wiring hidden, instead
of running it like that. But once again, that has zippo to do with it
being an electrocution risk. Personally, I wouldn't want an electric
heater in my shower regardless of how it was wired. I don't see a
GFCI anywhere. Did he put in a GFCI breaker in the panel? What
country are you in? I would think it would be a code requirement to
have a GFCI. I would definitely make sure there is a GFCI, as that
is key to avoid your electrocution scenario.

  #9   Report Post  
Posted to alt.home.repair
RBM
 
Posts: n/a
Default wiring for electric water heater

Not the prettiest job I've seen either, I think it would have made more
sense for him to have put a plug on the end of the cable so you could
disconnect it at will


"Ken" wrote in message
ups.com...
Thanks for the reply......i've uploaded some pics to give a better
idea. He stated that it takes a lot of work to connect to the
main...maybe have to go through the roof and all the way downstairs.
I'm staying in a double-storey terrace house. So he said it's easier to
get it from my room which has the attached bathroom. What bout the
story about the electrocuted couple that I heard from my father.
They've also done the same thing......dragged from the room socket. So
it's basically miswired for that case?


this is the socket in my room where it's being extended from
http://i83.photobucket.com/albums/j2...05-06_2358.jpg

this is the water heater switch in the bathroom
http://i83.photobucket.com/albums/j2...05-06_2356.jpg

and this is the water heater
http://i83.photobucket.com/albums/j2...05-06_2357.jpg



  #10   Report Post  
Posted to alt.home.repair
mm
 
Posts: n/a
Default wiring for electric water heater

On 9 May 2006 07:43:37 -0700, "Ken" wrote:

Thanks for the replies.....the heater that i'm using is a Pensonic
PWH767E. The power rating on the box says 3.6Kw 15A, 240 a.c.
50Hz....not sure if the info helps....I don't know if it's a small or
big heater. Anyway the problem isn't with the air-cond, I never and
don't plan to use the air-cond.


Then you don't have to worry about that, but you should be sure to
leave a detailed notation for the landlord and for the next tenant too
when you move out. They'll probably figure it out that you can't run
both at once, but they should know that that's the way it was
intended.

How big are the circuit breakers in your house, for this circuit and
for the others? 15A? 20?

That socket is purely meant for the
water heater and also my desktop computer. I'm also willing to turn off
my computer while the heater is on. So would that have any risk and
danger of electrocution? The water heater also comes with built-in
ELCB. Wouldn't the most that would happen be that the main switch be
tripped and besides that....there's also ELCB protection. How dangerous
is the electrocution part?


Don't pour hot water on your computer. (or cold water)

I'm just wondering if my father is being worried for no reason. I do
plan to have it fixed to the main power later but only when I'm free.
So for now should I stop using it because of this concern?




  #11   Report Post  
Posted to alt.home.repair
Don Young
 
Posts: n/a
Default wiring for electric water heater


"Ken" wrote in message
ups.com...
Thanks for the reply......i've uploaded some pics to give a better
idea. He stated that it takes a lot of work to connect to the
main...maybe have to go through the roof and all the way downstairs.
I'm staying in a double-storey terrace house. So he said it's easier to
get it from my room which has the attached bathroom. What bout the
story about the electrocuted couple that I heard from my father.
They've also done the same thing......dragged from the room socket. So
it's basically miswired for that case?


this is the socket in my room where it's being extended from
http://i83.photobucket.com/albums/j2...05-06_2358.jpg

this is the water heater switch in the bathroom
http://i83.photobucket.com/albums/j2...05-06_2356.jpg

and this is the water heater
http://i83.photobucket.com/albums/j2...05-06_2357.jpg

That heater looks to be located over the bathtub. If so, it may be a severe
electrocution hazard unless fed from a properly installed and tested GFCI
switch. It looks like the switch may be a GFCI type, but proper installation
and testing is critical.
Don Young


  #12   Report Post  
Posted to alt.home.repair
Chris Lewis
 
Posts: n/a
Default wiring for electric water heater

According to Don Young :

"Ken" wrote in message
ups.com...
Thanks for the reply......i've uploaded some pics to give a better
idea. He stated that it takes a lot of work to connect to the
main...maybe have to go through the roof and all the way downstairs.
I'm staying in a double-storey terrace house. So he said it's easier to
get it from my room which has the attached bathroom. What bout the
story about the electrocuted couple that I heard from my father.
They've also done the same thing......dragged from the room socket. So
it's basically miswired for that case?


this is the socket in my room where it's being extended from
http://i83.photobucket.com/albums/j2...05-06_2358.jpg

this is the water heater switch in the bathroom
http://i83.photobucket.com/albums/j2...05-06_2356.jpg

and this is the water heater
http://i83.photobucket.com/albums/j2...05-06_2357.jpg

That heater looks to be located over the bathtub. If so, it may be a severe
electrocution hazard unless fed from a properly installed and tested GFCI
switch. It looks like the switch may be a GFCI type, but proper installation
and testing is critical.


I don't think the switch is GFCI. Just UK-standard outlet switching.

UK wiring standards are very much different than ours with different voltages
than we're used to (almost everything is 240V) and various other unfamiliar
things like "ring mains" and rather different appliances.

I very much doubt that there are _any_ demand heaters that are appropriately
certified for installation _inside_ a shower enclosure in North America - even
with GFCI.

I would _hope_ this device is rated for this location - it may well have a builtin
GFCI.

If the instruction sheets or labeling on the device is accessible, I suggest
doing some research as to whether the device is appropriately rated for this
location.

In North America, demand heaters are usually tucked out of the way inside
enclosures. Eg: under the sink in a vanity, in a service room (eg: basement)
or wall unit with a door or a closet.
--
Chris Lewis, Una confibula non set est
It's not just anyone who gets a Starship Cruiser class named after them.
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Water heater in series to use as storage tank ... good or bad? Fred Home Repair 12 January 29th 05 01:38 PM
Power cost of idle electric water heater Phil Sherrod Home Repair 57 April 2nd 04 10:51 PM
Power cost of idle electric water heater Phil Sherrod Home Ownership 50 April 2nd 04 04:55 PM
Cost to install gas hot water heater Walleye Home Ownership 8 September 10th 03 03:20 AM
hot water recirculator, instant hot water but not a water heating unit, saves water, gas, time, money HeatMan Home Repair 0 August 24th 03 12:26 PM


All times are GMT +1. The time now is 09:12 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"