Home Repair (alt.home.repair) For all homeowners and DIYers with many experienced tradesmen. Solve your toughest home fix-it problems.

 
 
LinkBack Thread Tools Search this Thread Display Modes
Prev Previous Post   Next Post Next
  #1   Report Post  
Posted to alt.home.repair
 
Posts: n/a
Default Inductive coupling, house wiring, DMMs?

Folks:

I was going over an old circuit of mixed knob & tube and early NM,
replacing old receptacles and switches (ancient P&S) and upgrading
some wall-mounted fixtures (early 30s Markel Electric). The splices
are well-soldered and taped; the K&T has intact insulation, and for
once there was a reasonable amount of slack left to pull into new
plastic boxes -- and capped-off gas pipes from the original lighting
system...


With all the loads removed from the circuit, and the fuse removed,
I measured no continuity from hot to system ground (good), and
excellent continuity from neutral to system ground (also good). (I
had a 3-wire extension cord plugged into a newer circuit in the same
house). Nice to see the neutrals were still properly color coded.


Now, one of the Markel lights was fed by a run of K&T, which was
soldered to the fixture feeders and a run of 1950s NM, said splice
being buried in some kind of AWFUL white plastery substance as
hard and unmerciful as death and taxes (my best guess is it was white
lead putty). Into a plastic box this all went, ready to join the brand
spanking new fixture leads.


For good measure, I took my DMM and measured AC volts between
another circuit's hot side (from the extension cord) to the K&T
neutral. 120 V, fine. Then I measured between the cord's hot to the
K&T hot. 120V? Wha? I rechecked with a neon lamp. The lamp
lit. The NM conductors, which ran through two 3-way switches
to another light fixture, which was off, read 79v each. Wha?


I don't get it. The circuit is definitely dead. I have accounted for
all the
other branches, some of which are multiwire, but this one is not.
Everything is turned off, and indeed there seems to be no DC path to
ground through the K&T hot, and certainly not through the disconnected
run to the 3-way switched fixture!


What does everyone think? Inductive coupling? Would that light the
neon bulb? Should I go back to my old analog meter?

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Question on capacitive and inductive pick-up wiring to BNC's. yoda439 Electronics Repair 4 January 22nd 05 06:34 AM
more fun with air conditioning J Jensen Home Repair 93 September 7th 04 10:39 AM
Outside wiring: a long distance from house scouser UK diy 7 August 27th 03 09:14 PM
Green ooze from house wiring roger UK diy 18 August 14th 03 11:22 PM
Ceiling rose wiring old house Driving me mad arr Toby UK diy 1 July 9th 03 03:20 PM


All times are GMT +1. The time now is 11:28 AM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
Copyright ©2004-2024 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"